Try the full study dashboard free, no signup: practice, flashcards and your Exam Readiness Score. Open it →
Home / Practice tests / PE Fire Protection
NCEES PE · Last updated November 2026

PE Fire Protection: free practice test

The licensing exam for US fire protection engineers, given on a single day each year. New specifications start with the April 2027 exam: eight knowledge areas, with energy storage systems now listed and NFPA 855 added to the supplied standards. Water-based systems (12-18 questions) is the largest area. Answers that reference a standard are scored to the listed edition.

Watch the free 4:13 video lesson: the key PE Fire Protection concepts →

Premium: 3,000 practice questions, 6 full mock exams, 800 flashcards and 60 comprehensive key notes, topic by topic. See the study path ·

Or open the free PE Fire Protection study dashboard: flashcards, notes and your Readiness Score, no signup →

About the PE Fire Protection exam

The licensing exam for US fire protection engineers, given on a single day each year. New specifications start with the April 2027 exam: eight knowledge areas, with energy storage systems now listed and NFPA 855 added to the supplied standards. Water-based systems (12-18 questions) is the largest area. Answers that reference a standard are scored to the listed edition.

What's on the exam

PE Fire Protection
Fire Protection Analysis
7 key facts
Fire Science
7 key facts
Smoke Control Systems
7 key facts
Fire Alarm and Signaling Systems
7 key facts
Water-Based Fire Protection Systems
7 key facts
Special Hazard Systems
7 key facts
Passive and Structural Fire Protection
7 key facts
Human Behavior and Evacuation
7 key facts

Each branch is a topic in the official outline. Members see every key fact on the full mind map. Read the free study guide →

How to pass the PE Fire Protection exam

  • 85 questions in 8.5 hours is 6 minutes each, but searching supplied PDFs takes time. Practice in the searchable PDFs rather than in printed books.
  • The supplied standards are searchable PDFs with linked chapters, so learn which chapter holds each topic before exam day.
  • Use the current standards list. NFPA 12 and NFPA 25 have dropped off it, NFPA 855 has been added and every other listed edition has changed.
  • Book your Pearson seat as soon as your board approves you, because there is only one sitting per year.

Save your results and get your Readiness Score

Create a free account after the test: your score by topic, a mistakes bank, the complete study notes for the first topic, flashcards and the Fire Protection Formulas & Values Sheet.

Take the test first

What's in the premium PE Fire Protection prep

Premium PE Fire Protection prep is studied one topic at a time. Each step starts with that topic's key notes and flashcard deck, then its own question sets of 25, so you master one topic before you move to the next. When every topic is strong, the 6 full mock exams show you're ready.

3,000practice questions, every answer explained
6full-length mock exams, 85 questions each, timed
800flashcards with spaced repetition, sorted by topic
60comprehensive key notes across 8 topics

Your step-by-step study path

  1. 1
    Fire Protection Analysis8 key notes, 100 flashcards, then 375 practice questions in 15 sets of 25
    Notes free with an account
  2. 2
    Fire Science8 key notes, 100 flashcards, then 375 practice questions in 15 sets of 25
    Premium
  3. 3
    Smoke Control Systems8 key notes, 100 flashcards, then 375 practice questions in 15 sets of 25
    Premium
  4. 4
    Fire Alarm and Signaling Systems8 key notes, 100 flashcards, then 375 practice questions in 15 sets of 25
    Premium
  5. 5
    Water-Based Fire Protection Systems7 key notes, 100 flashcards, then 375 practice questions in 15 sets of 25
    Premium
  6. 6
    Special Hazard Systems7 key notes, 100 flashcards, then 375 practice questions in 15 sets of 25
    Premium
  7. 7
    Passive and Structural Fire Protection7 key notes, 100 flashcards, then 375 practice questions in 15 sets of 25
    Premium
  8. 8
    Human Behavior and Evacuation7 key notes, 100 flashcards, then 375 practice questions in 15 sets of 25
    Premium
  9. Final step: 6 full mock exams85 questions each, timed like test day. Pass them, then book your exam.
    Premium
Free with an account

Read the complete PE Fire Protection study notes for “Fire Protection Analysis”

Our first full set of comprehensive notes, about 15 minutes of reading: Performance-based design · Fire risk assessment · Fire models · Energy storage systems, a worked exam example, the traps examiners use and a one-minute recap. Create a free account to read it and see how premium notes work before you decide.

Open the free dashboard

Study tools included

3,000 practice questions

3,000 exam-style questions per exam, organized topic by topic in sets of 25. Every answer explained, with the rule it comes from.

6 full mock exams

6 full-length timed mock exams per exam, with real question counts and time limits, so test day feels like practice day.

Exam Readiness Score

One 0 to 100 number that tells you when you're ready to book. Reach 80 and you're covered by our Pass Guarantee.

800 flashcards + spaced repetition

800 flashcards per exam, in a deck for each topic, that come back right before you'd forget them. Five minutes a day keeps every number fresh.

60 comprehensive key notes

60 key notes per exam, split across its topics and each explained in full: the concepts, worked exam examples, the traps examiners use and a quick recap. Your first set is free with an account.

Mind maps

See the whole exam on one screen: every topic and the facts under it.

Sample questions with answers

These are the questions in the free test above, with answers. Try the test first. You'll learn more by getting some wrong.

1. A risk analysis uses an event tree. Fires start in a space at 0.02 per year. The sprinkler system fails on demand with probability 0.04, and the on-site brigade fails to control the fire with probability 0.3. What is the annual frequency of an uncontrolled fire?
Answer: 2.4 x 10^-4 per year. An uncontrolled fire needs the initiating fire and both failures, so multiply along that branch: 0.02 x 0.04 x 0.3 = 2.4 x 10^-4 per year. Using one failure alone gives 8.0 x 10^-4 or 6.0 x 10^-3. Multiplying by success probabilities gives about 1.3 x 10^-2, which is the fully controlled branch.
2. A reviewer of a lithium-ion energy storage layout needs test data on whether thermal runaway in one unit spreads to adjacent units. Cell-level and module-level UL 9540A reports are on file. Which additional report answers the question?
Answer: A unit-level UL 9540A report. UL 9540A tests in steps: cell (thermal runaway behavior and gases), module (propagation within a module), unit (propagation between units), and installation (effectiveness of fire protection). Only unit-level data addresses unit-to-unit spread. NFPA 855 relies on these reports when spacing or protection differs from the prescriptive layout.
3. A design fire follows Q = alpha t^2 with fast growth, alpha = 0.0469 kW/s^2. How long after effective ignition does it reach 2,000 kW?
Answer: 207 s. Rearranging gives t = (Q / alpha)^0.5 = (2,000 / 0.0469)^0.5 = 207 s. The 150 s value is the fast-fire time to about 1,055 kW, a common memory slip. Ultrafast and medium growth give 103 s and 413 s for this heat release rate.
4. A 1,000 kW pool fire has a radiative fraction of 0.30. Using the point source model, what is the incident heat flux on a target 3 m from the point source?
Answer: 2.7 kW/m^2. The point source model gives q'' = (radiative fraction x Q) / (4 pi R^2) = 300 / (4 pi x 9) = 2.65 kW/m^2. Omitting the radiative fraction gives 8.8 kW/m^2, and failing to square the radius gives 8.0 kW/m^2. The model is reasonable only when the target is far from the flames compared with the fire diameter.
5. An atrium has a design fire of 5,000 kW total with a convective fraction of 0.7. Using the NFPA 92 axisymmetric plume correlation for z above the limiting flame height, what is the mass flow at a smoke layer interface 15 m above the fuel?
Answer: 105 kg/s. Qc = 0.7 x 5,000 = 3,500 kW and the limiting height is 0.166 Qc^(2/5) = 4.3 m, so the upper correlation applies. m = 0.071 Qc^(1/3) z^(5/3) + 0.0018 Qc = 98.3 + 6.3 = 105 kg/s. Using total heat release gives 120 kg/s, and dropping the second term gives 98 kg/s.
6. A non-voice fire alarm panel draws 0.25 A in standby and 3.0 A in alarm. Under NFPA 72, with 24 hours of standby, 5 minutes of alarm and the required 20% safety margin, what is the minimum battery capacity?
Answer: 7.5 Ah. Standby is 0.25 x 24 = 6.0 Ah and alarm is 3.0 x 5/60 = 0.25 Ah, for 6.25 Ah. Adding the 20% margin gives 7.5 Ah. The 8.1 Ah result comes from using a 15-minute alarm period, which is the requirement for voice evacuation systems.
7. A notification circuit carries a 2.0 A load at its end on 12 AWG wire at 1.93 ohms per 1,000 ft. Supply at the panel is 20.4 V at end-of-battery conditions, and devices need at least 16 V. What is the maximum one-way circuit length?
Answer: 570 ft. Allowable drop is 20.4 - 16 = 4.4 V. Resistance covers both conductors, so length = 4.4 / (2 x 2.0 x 1.93/1,000) = 570 ft. Counting one conductor gives 1,140 ft, and starting from a nominal 24 V gives about 1,040 ft. End-of-battery voltage is the conservative basis for the calculation.
8. An Ordinary Hazard Group 2 system is designed at 0.20 gpm/ft^2. The most remote sprinkler is K-5.6 and covers 130 ft^2. What is the minimum pressure at that sprinkler?
Answer: 21.6 psi. Required flow is 0.20 x 130 = 26 gpm. From Q = K p^0.5, p = (26 / 5.6)^2 = 21.6 psi. The 7 psi figure is the NFPA 13 minimum operating pressure, which only governs if the density needs less. The 4.6 result forgets to square Q/K.
9. A hydrant flow test shows 70 psi static and 50 psi residual at 1,000 gpm. Using the standard water supply curve with the 1.85 exponent, what pressure is available at a demand of 900 gpm?
Answer: 53.5 psi. Pressure drop scales with Q^1.85: drop = 20 x (900/1,000)^1.85 = 16.5 psi, so available pressure is 70 - 16.5 = 53.5 psi. A straight-line estimate gives 52.0 psi, which understates the supply. Using the 0.54 exponent here gives 51.1 psi: 0.54 applies when solving for flow, not pressure.
10. A horizontal fire pump is rated at 1,000 gpm and 100 psi net. Acceptance data shows 130 psi net at churn and 62 psi net at 1,500 gpm. How should the test be judged under NFPA 20?
Answer: Fail, because net pressure at 150% flow is below 65% of rated. A horizontal centrifugal fire pump must deliver at least 65% of rated pressure at 150% of rated flow, here 65 psi at 1,500 gpm, and 62 psi falls short. Churn may be up to 140% of rated pressure, so 130 psi is acceptable. A pump can look fine at rated flow and still fail at overload.
11. A 5,000 ft^3 room at 70 F is protected by HFC-227ea at 7.0% by volume, with specific vapor volume s = 1.885 + 0.0046T in ft^3/lb. What agent weight is needed before any altitude correction?
Answer: 170.5 lb. s = 1.885 + 0.0046(70) = 2.207 ft^3/lb, and W = (V/s) x C/(100 - C) = (5,000/2.207) x (7/93) = 170.5 lb. Using C/100 gives 158.6 lb, which ignores the agent's displacement of vented air. Use the minimum expected enclosure temperature when the design calls for it, as that raises the required weight.
12. An 80 ft diameter fixed-roof hydrocarbon tank has Type II foam outlets designed at 0.10 gpm/ft^2 for 55 minutes with 3% concentrate. Excluding supplementary hose streams and piping, how much concentrate is needed?
Answer: 829 gal. Area is pi x 40^2 = 5,027 ft^2, so solution flow is 503 gpm and concentrate flow is 3% of that, 15.1 gpm. Over 55 minutes that is 829 gal. A 30-minute period gives 452 gal, and 2% concentrate gives 553 gal. NFPA 11 also requires supplementary hose streams, which add to the total.
13. A sprayed fire-resistive design requires 1.00 in. on a beam with W/D = 0.80. A substitute beam has W/D = 0.60. Using h2 = h1 (W1/D1 + 0.6) / (W2/D2 + 0.6), what thickness does the substitute beam need?
Answer: 1.17 in.. h2 = 1.00 x (0.80 + 0.6) / (0.60 + 0.6) = 1.17 in. A lighter section heats faster, so it needs more protection. A thickness below 1.00 in. inverts the ratio, and the equation only applies within the limits of the listed design.
14. A 7,000 ft^2 net assembly room uses concentrated seating without fixed seats at 7 ft^2 per person. Using 0.2 in. per person, what minimum clear width must the main entrance provide under NFPA 101?
Answer: 100 in.. Occupant load is 7,000 / 7 = 1,000, which needs 200 in. of total egress capacity at 0.2 in. per person. In assembly occupancies the main entrance must accommodate half the total occupant load, so 100 in. The 67 in. value divides by three because the room has three required exits, but the main entrance rule is one-half.
15. In a hydraulic egress calculation, 300 people leave through a door 1.2 m wide. The boundary layer is 150 mm on each side and the specific flow is 1.32 persons/s per m of effective width. How long does the flow take?
Answer: 253 s. Effective width is 1.2 - 0.30 = 0.90 m, so flow is 1.32 x 0.90 = 1.19 persons/s and time is 300 / 1.19 = 253 s. Using the clear 1.2 m width gives 189 s, which is unconservative. Total evacuation time also needs detection, pre-movement and travel time.

Get the full PE Fire Protection prep

Most popular · cancel anytime

Premium Monthly

$147/month
per exam
About $4.83 a day · less than a single code book, for a certification employers and AHJs ask for by name
  • One NFPA exam of your choice: CFPS, CFI or CFPE
  • 3,000 practice questions + 6 full mock exams per exam
  • 800 flashcards + 60 key notes per exam, by topic, plus mind maps
  • Spaced repetition + mistakes bank
  • Readiness Score & detailed reports
  • Video lessons as they release
  • Content updates during your access
  • 5 bonuses: formulas and values sheet, code values quick reference, study planner and more
  • Pass Guarantee: complete the prep, pass or 100% back

Renews monthly until you cancel. Cancel in two clicks from your account; you keep access until the end of the month you've paid for. No minimum term.

Best value · 3 months free

Premium Yearly

$1,323/year
per exam
Pay for 9 months, get 12. Save $441 against paying monthly.
  • One NFPA exam of your choice: CFPS, CFI or CFPE
  • 3,000 practice questions + 6 full mock exams per exam
  • 800 flashcards + 60 key notes per exam, by topic, plus mind maps
  • Spaced repetition + mistakes bank
  • Readiness Score & detailed reports
  • Video lessons as they release
  • Content updates during your access
  • 5 bonuses: formulas and values sheet, code values quick reference, study planner and more
  • Pass Guarantee: complete the prep, pass or 100% back

Renews once a year until you cancel. We email you before each renewal. Cancel any time from your account; you keep access until the end of the year you've paid for.

Pass Guarantee. Complete the full prep, sit your exam within 60 days, and if you don't pass we refund 100% of your subscription payments. See the requirements
Secure checkout by Stripe Card, Apple Pay, Google Pay Pass Guarantee

PE Fire Protection exam FAQ

How many questions are on the PE Fire Protection exam?

85 questions, with a time limit of 9.5-hour appointment: 2-minute nondisclosure agreement, 8-minute tutorial, 8.5 hours of exam and a 50-minute scheduled break. Format: closed book with electronic references: the pe fire protection reference handbook and, where a question needs them, nfpa 11, 13, 20, 30, 72, 92, 101, 400, 855 and 2001, all supplied on screen. personal copies are not allowed. questions use both si and us customary units. the real exam has multiple-choice questions and alternative item types; this prep uses 4-option single-best-answer questions.

What is the passing score for PE Fire Protection?

Not published by NCEES. Results are reported as pass or fail.

How much does the PE Fire Protection exam cost?

US$400 exam fee paid to NCEES. Some licensing boards charge a separate application fee. Fees and reference editions change, so confirm on nfpa.org before you apply.

Which languages is the PE Fire Protection exam offered in?

English. NCEES does not list other languages for this exam; confirm with NCEES.

Where do I take the PE Fire Protection exam?

Pearson VUE test centers, computer-based, on one day per year (next test date April 13, 2027). Seats may be reserved up to a year ahead once registered with NCEES and approved by your board.

Is this PE Fire Protection practice test free?

Yes. The 15-question practice test on this page is free, with an explanation for every answer and no signup. A free account also unlocks the complete study notes for the first topic. The full PE Fire Protection prep is Premium at $147 a month for this exam.

What's in the premium PE Fire Protection prep?

3,000 practice questions organized topic by topic (Fire Protection Analysis: 375; Fire Science: 375; Smoke Control Systems: 375; Fire Alarm and Signaling Systems: 375; Water-Based Fire Protection Systems: 375; Special Hazard Systems: 375; Passive and Structural Fire Protection: 375; Human Behavior and Evacuation: 375), 6 full-length timed mock exams of 85 questions, 800 flashcards and 60 comprehensive key notes split across all 8 topics, plus a mistakes bank and the Readiness Score.

Related practice tests

Exam details are summarized from the official candidate information available in November 2026. NFPA changes formats and fees, so confirm with National Council of Examiners for Engineering and Surveying (NCEES), with approval by your state licensing board before you book. CFPSExamPrep is not affiliated with NFPA or Prometric.

Start the free test