NAFED Pre-engineered Kitchen Fire Suppression (FK): free practice test

The ICC/NAFED credential for technicians who lay out, install, inspect and service pre-engineered wet chemical systems over commercial cooking equipment. It is based on NFPA 17A and NFPA 96, with maintenance and recharge (32%) and general component requirements (25%) carrying over half the marks. Certification is valid for three years and renewals are handled by NAFED.

Watch the free 4:16 video lesson: the key NAFED FK Kitchen Suppression concepts →

Premium: 3,000 practice questions, 6 full mock exams, 800 flashcards and 60 comprehensive key notes, topic by topic. See the study path ·

Or open the free NAFED FK Kitchen Suppression study dashboard: flashcards, notes and your Readiness Score, no signup →

About the NAFED FK Kitchen Suppression exam

The ICC/NAFED credential for technicians who lay out, install, inspect and service pre-engineered wet chemical systems over commercial cooking equipment. It is based on NFPA 17A and NFPA 96, with maintenance and recharge (32%) and general component requirements (25%) carrying over half the marks. Certification is valid for three years and renewals are handled by NAFED.

What's on the exam

NAFED FK Kitchen Suppression
Maintenance and Recharge
7 key facts
General Component Requirements
7 key facts
Installations and Acceptance Testing
6 key facts
Hazard Identification
6 key facts
Hoods and Exhaust Systems
7 key facts
Administration and Records
6 key facts
Inspection
6 key facts

Each branch is a topic in the official outline. Members see every key fact on the full mind map. Read the free study guide →

How to pass the NAFED FK Kitchen Suppression exam

  • 80 questions in 2 hours is 90 seconds each. Know the semiannual, annual and 12-year intervals without looking them up.
  • Maintenance and recharge is almost a third of the exam: tab the NFPA 17A inspection, maintenance and hydrostatic testing chapter.
  • Many questions are really NFPA 96 questions: fuel shutoff, manual actuation, alarm interconnection, filters and hood clearances. Tab NFPA 96 Chapters 6, 10 and 12.
  • The kitchen exam and the industrial (FN) exam may use different editions of NFPA 17A and 96. Study from the edition your exam lists.

Save your results and get your Readiness Score

Create a free account after the test: your score by topic, a mistakes bank, the complete study notes for the first topic, flashcards and the Fire Protection Formulas & Values Sheet.

Take the test first

What's in the premium NAFED FK Kitchen Suppression prep

Premium NAFED FK Kitchen Suppression prep is studied one topic at a time. Each step starts with that topic's key notes and flashcard deck, then its own question sets of 25, so you master one topic before you move to the next. When every topic is strong, the 6 full mock exams show you're ready.

3,000practice questions, every answer explained
6full-length mock exams, 80 questions each, timed
800flashcards with spaced repetition, sorted by topic
60comprehensive key notes across 7 topics

Your step-by-step study path

  1. 1
    Maintenance and Recharge9 key notes, 115 flashcards, then 450 practice questions in 18 sets of 25
    Notes free with an account
  2. 2
    General Component Requirements9 key notes, 115 flashcards, then 425 practice questions in 17 sets of 25
    Premium
  3. 3
    Installations and Acceptance Testing9 key notes, 115 flashcards, then 425 practice questions in 17 sets of 25
    Premium
  4. 4
    Hazard Identification9 key notes, 115 flashcards, then 425 practice questions in 17 sets of 25
    Premium
  5. 5
    Hoods and Exhaust Systems8 key notes, 115 flashcards, then 425 practice questions in 17 sets of 25
    Premium
  6. 6
    Administration and Records8 key notes, 115 flashcards, then 425 practice questions in 17 sets of 25
    Premium
  7. 7
    Inspection8 key notes, 110 flashcards, then 425 practice questions in 17 sets of 25
    Premium
  8. Final step: 6 full mock exams80 questions each, timed like test day. Pass them, then book your exam.
    Premium
Free with an account

Read the complete NAFED FK Kitchen Suppression study notes for “Maintenance and Recharge”

Our first full set of comprehensive notes, about 15 minutes of reading: Semiannual maintenance · Nozzles, piping and coverage · Recharge after discharge · Hydrostatic testing and upgrades, a worked exam example, the traps examiners use and a one-minute recap. Create a free account to read it and see how premium notes work before you decide.

Open the free dashboard

Study tools included

3,000 practice questions

3,000 exam-style questions per exam, organized topic by topic in sets of 25. Every answer explained, with the rule it comes from.

6 full mock exams

6 full-length timed mock exams per exam, with real question counts and time limits, so test day feels like practice day.

Exam Readiness Score

One 0 to 100 number that tells you when you're ready to book. Reach 80 and you're covered by our Pass Guarantee.

800 flashcards + spaced repetition

800 flashcards per exam, in a deck for each topic, that come back right before you'd forget them. Five minutes a day keeps every number fresh.

60 comprehensive key notes

60 key notes per exam, split across its topics and each explained in full: the concepts, worked exam examples, the traps examiners use and a quick recap. Your first set is free with an account.

Mind maps

See the whole exam on one screen: every topic and the facts under it.

Sample questions with answers

These are the questions in the free test above, with answers. Try the test first. You'll learn more by getting some wrong.

1. At a semiannual service, the fusible links on a wet chemical kitchen system look clean and undamaged. They were installed 6 months ago. What must the technician do?
Answer: Replace them and record the links' manufacture and installation dates. NFPA 17A requires fusible metal alloy sensing elements to be replaced at least semiannually, whatever they look like, and the removed links destroyed. The year of manufacture and installation date are recorded on the service tag. Appearance is not a test of whether a link will fuse at its rating.
2. A kitchen system uses frangible glass-bulb detectors instead of fusible links. What does NFPA 17A require for these sensing elements?
Answer: Inspect and clean or replace them as needed at least every 12 months. Fixed-temperature elements other than fusible metal alloy types may remain in service provided they are inspected and cleaned, or replaced if needed, per the manufacturer at least every 12 months. The semiannual replacement rule applies to fusible alloy links.
3. During a 2026 semiannual service, the technician finds the wet chemical agent container was manufactured in 2013 and has never been hydrostatically tested. What is required?
Answer: The 12-year test is overdue for the container, hoses and auxiliary cylinders. NFPA 17A requires wet chemical containers, auxiliary pressure containers and hose assemblies to be hydrostatically tested at intervals of not more than 12 years. A 2013 container was due in 2025, so it is overdue and should be tested or replaced now, not deferred.
4. A restaurant replaces a two-burner range under its existing kitchen system with a 40-lb fryer. The system's gauge and seals are fine. What is required before frying begins?
Answer: Evaluate the system and change nozzles and detection to protect the fryer per the listing. When the protected hazard changes, the system must be evaluated and altered to protect the new appliance as the manufacturer's listing requires, since fryers need specific nozzles, positions and flow points. A Class K extinguisher supplements the fixed system but never replaces it.
5. After a system test, the technician replaces the test link and resets the release. The mechanical gas valve reopens by itself as soon as the release is reset. What is the problem?
Answer: Fuel shutoff devices must require manual reset after system operation. NFPA 96 requires all fuel and electric power to the protected equipment to shut off automatically when the system operates, and the shutoff devices must need a manual reset. A valve that reopens on its own could restore gas to a fire area.
6. When a kitchen system discharges, what should happen to the hood exhaust fan in a standard installation under NFPA 96?
Answer: It keeps running unless the listing or design requires shutdown. NFPA 96 keeps exhaust fans running after the extinguishing system operates unless shutdown is required by a listed component or by the system's design. Running fans help carry smoke and heat out and keep the duct under negative pressure.
7. A kitchen system is installed in a building that has a fire alarm system. What does NFPA 96 require when the kitchen system operates?
Answer: It must activate the building fire alarm signaling system. Where a building has a fire alarm system, operation of the kitchen extinguishing system must activate it, so occupants are warned and the event is reported. A local horn alone does not satisfy that requirement.
8. An installer plans to mount the remote manual pull station 60 in. above the floor beside the fryer, behind the cook line. What is wrong with this location?
Answer: It must be 42 to 48 in. high, in a path of egress, and labeled. NFPA 96 puts the manual actuation device 42 to 48 in. above the floor, where it can be reached in a fire, in a path of egress, and labeled with the hazard it protects. Beside the fryer, a cook may not be able to reach it once a fire starts.
9. A newly installed wet chemical system is ready for acceptance. Which check is essential before the technician signs off?
Answer: Operating both actuation means and confirming fuel and power shutoff. Acceptance testing proves the system works as installed: automatic and manual actuation operate, fuel and electric power to protected appliances shut off, and any alarm interconnection works, following the manufacturer's test procedures. A new container does not need a hydrostatic test.
10. A new deep fat fryer is being placed next to a range with open burners. What separation does NFPA 96 require?
Answer: At least 16 in. from the flames, or a steel or tempered glass baffle at least 8 in. high. A deep fat fryer must have at least 16 in. of space from the surface flames of adjacent cooking equipment, or a steel or tempered glass baffle at least 8 in. high between them. Shared protection does not remove the risk of hot oil being ignited by open flames.
11. Staff often roll a fryer on casters away from the line to clean behind it. What must be provided to keep the fryer protected?
Answer: A means to return the fryer to its design position under the nozzle. Appliances on casters must have a means, such as a restraint or position marker, to make sure they return to the position the system was designed to protect. A fryer left out of position can sit outside nozzle coverage.
12. A gas charbroiler without a listed exhaust hood is installed under a hood with grease filters. What is the minimum height from the cooking surface to the lower edge of the filters?
Answer: 4 ft. NFPA 96 requires at least 18 in. between grease removal devices and the cooking surface in general, but 4 ft for charcoal and charcoal-type broilers, including gas or electric charbroilers. The extra height keeps flare-ups from igniting grease in the filters.
13. During service, the technician finds mesh grease filters installed in a standard (unlisted) hood. What should be reported?
Answer: Mesh filters are not permitted there; replace them with listed filters. NFPA 96 requires listed grease filters or approved grease removal devices; mesh filters are not permitted unless they are part of a listed hood or listed with a primary filter. Grease that passes mesh filters loads the duct, where a fire is much harder to control.
14. A technician has prepared the layout for a new kitchen system in a remodeled restaurant, following the manufacturer's listing. What is the next administrative step?
Answer: Submit the layout to the AHJ for review or permit before installing. NAFED's outline expects the technician to identify the authority having jurisdiction and submit the prepared layout before installation, then document the system as installed. Installing first risks rework if the AHJ requires changes.
15. During a monthly check, the kitchen manager sees that a nozzle blow-off cap is missing. The gauge is in the green and the seals are intact. What should happen?
Answer: The servicing company should be called to correct it. Monthly inspection includes checking that blow-off caps are intact, because they keep grease out of nozzle orifices. A missing cap is a deficiency for the servicing company to correct promptly; taping or removing a nozzle disables protection.

Get the full NAFED FK Kitchen Suppression prep

Most popular · cancel anytime

Premium Monthly

$147/month
per exam
About $4.83 a day · less than a single code book, for a certification employers and AHJs ask for by name
  • One NFPA exam of your choice: CFPS, CFI or CFPE
  • 3,000 practice questions + 6 full mock exams per exam
  • 800 flashcards + 60 key notes per exam, by topic, plus mind maps
  • Spaced repetition + mistakes bank
  • Readiness Score & detailed reports
  • Video lessons as they release
  • Content updates during your access
  • 5 bonuses: formulas and values sheet, code values quick reference, study planner and more
  • Pass Guarantee: complete the prep, pass or 100% back

Renews monthly until you cancel. Cancel in two clicks from your account; you keep access until the end of the month you've paid for. No minimum term.

Best value · 3 months free

Premium Yearly

$1,323/year
per exam
Pay for 9 months, get 12. Save $441 against paying monthly.
  • One NFPA exam of your choice: CFPS, CFI or CFPE
  • 3,000 practice questions + 6 full mock exams per exam
  • 800 flashcards + 60 key notes per exam, by topic, plus mind maps
  • Spaced repetition + mistakes bank
  • Readiness Score & detailed reports
  • Video lessons as they release
  • Content updates during your access
  • 5 bonuses: formulas and values sheet, code values quick reference, study planner and more
  • Pass Guarantee: complete the prep, pass or 100% back

Renews once a year until you cancel. We email you before each renewal. Cancel any time from your account; you keep access until the end of the year you've paid for.

Pass Guarantee. Complete the full prep, sit your exam within 60 days, and if you don't pass we refund 100% of your subscription payments. See the requirements
Secure checkout by Stripe Card, Apple Pay, Google Pay Pass Guarantee

NAFED FK Kitchen Suppression exam FAQ

How many questions are on the NAFED FK Kitchen Suppression exam?

80 multiple-choice questions, with a time limit of 2 hours. Format: open book. nafed's references: nfpa 17a, standard for wet chemical extinguishing systems and nfpa 96, standard for ventilation control and fire protection of commercial cooking operations, plus nafed's fire and fire extinguishment (optional). manufacturers' manuals are not listed references. the exam is written only; this prep does not cover hands-on or manufacturer training.

What is the passing score for NAFED FK Kitchen Suppression?

Scaled score of 75. ICC reports PASS only; failing candidates see the topic areas where they were weak.

How much does the NAFED FK Kitchen Suppression exam cost?

US$320 (NAFED, 2026). Exam purchases are final and valid for 365 days. Fees and reference editions change, so confirm on nfpa.org before you apply.

Which languages is the NAFED FK Kitchen Suppression exam offered in?

English. ICC and NAFED do not list other languages; confirm with ICC.

Where do I take the NAFED FK Kitchen Suppression exam?

ICC, by proctored online testing (PRONTO). Register through the ICC Exam Catalog under the NAFED category.

Is this NAFED FK Kitchen Suppression practice test free?

Yes. The 15-question practice test on this page is free, with an explanation for every answer and no signup. A free account also unlocks the complete study notes for the first topic. The full NAFED FK Kitchen Suppression prep is Premium at $147 a month for this exam.

What's in the premium NAFED FK Kitchen Suppression prep?

3,000 practice questions organized topic by topic (Maintenance and Recharge: 450; General Component Requirements: 425; Installations and Acceptance Testing: 425; Hazard Identification: 425; Hoods and Exhaust Systems: 425; Administration and Records: 425; Inspection: 425), 6 full-length timed mock exams of 80 questions, 800 flashcards and 60 comprehensive key notes split across all 7 topics, plus a mistakes bank and the Readiness Score.

Related practice tests

Exam details are summarized from the official candidate information available in November 2026. NFPA changes formats and fees, so confirm with National Association of Fire Equipment Distributors (NAFED), in a joint program with the International Code Council (ICC), which administers the exam before you book. CFPSExamPrep is not affiliated with NFPA or Prometric.