Certified Electrical Safety Compliance Professional (CESCP): free practice test

NFPA's certification for people who run electrical safety programs or train and manage workers exposed to electrical hazards. It is an open-book exam on NFPA 70E, weighted Work Involving Electrical Hazards 31%, Electrical Safety Programs 30%, Establishing an Electrically Safe Work Condition 29% and Special Equipment 10%. Candidates need 40 hours of electrical safety training in the last 3 years plus a qualifying experience route.

Watch the free 4:27 video lesson: the key NFPA CESCP concepts →

Premium: 3,000 practice questions, 6 full mock exams, 800 flashcards and 60 comprehensive key notes, topic by topic. See the study path ·

Or open the free NFPA CESCP study dashboard: flashcards, notes and your Readiness Score, no signup →

About the NFPA CESCP exam

NFPA's certification for people who run electrical safety programs or train and manage workers exposed to electrical hazards. It is an open-book exam on NFPA 70E, weighted Work Involving Electrical Hazards 31%, Electrical Safety Programs 30%, Establishing an Electrically Safe Work Condition 29% and Special Equipment 10%. Candidates need 40 hours of electrical safety training in the last 3 years plus a qualifying experience route.

What's on the exam

NFPA CESCP
Electrical Safety Program and Employer Responsibilities
8 key facts
Risk Assessment, Training, Audits and Maintenance
7 key facts
Lockout/Tagout Program and Procedures
7 key facts
Verifying an Electrically Safe Work Condition and Temporary Grounding
7 key facts
Justifying Energized Work, Permits and Shock Risk Assessment
7 key facts
Arc Flash Risk Assessment, Labels and PPE
7 key facts
Special Equipment: Batteries, Lasers, Power Electronics, Laboratories, Capacitors and Cells
7 key facts

Each branch is a topic in the official outline. Members see every key fact on the full mind map. Read the free study guide →

How to pass the NFPA CESCP exam

  • Bring the edition of NFPA 70E named by the exam body, not an older or newer one. Section numbers moved between editions: the electrically safe work condition steps are in 120.6 in the current edition, and the program requirements are in 110.3.
  • Plan for 110 questions in 3 hours, about 98 seconds each, since NFPA's Program Overview gives that count. Tab Article 110, Article 120, and the shock and arc flash tables in Article 130 before test day.
  • The blueprint is written from a program owner's view: audits, documentation, who is responsible and what a permit must contain. Read each scenario for the compliance failure, not just the technical fact.
  • Special Equipment is only 10%, but Chapter 3 is unfamiliar to many candidates. Learn the thresholds in Articles 320, 330 and 360 so you can find them quickly.

Save your results and get your Readiness Score

Create a free account after the test: your score by topic, a mistakes bank, the complete study notes for the first topic, flashcards and the Fire Protection Formulas & Values Sheet.

Take the test first

What's in the premium NFPA CESCP prep

Premium NFPA CESCP prep is studied one topic at a time. Each step starts with that topic's key notes and flashcard deck, then its own question sets of 25, so you master one topic before you move to the next. When every topic is strong, the 6 full mock exams show you're ready.

3,000practice questions, every answer explained
6full-length mock exams, 2026 questions each, timed
800flashcards with spaced repetition, sorted by topic
60comprehensive key notes across 7 topics

Your step-by-step study path

  1. 1
    Electrical Safety Program and Employer Responsibilities9 key notes, 115 flashcards, then 450 practice questions in 18 sets of 25
    Notes free with an account
  2. 2
    Risk Assessment, Training, Audits and Maintenance9 key notes, 115 flashcards, then 425 practice questions in 17 sets of 25
    Premium
  3. 3
    Lockout/Tagout Program and Procedures9 key notes, 115 flashcards, then 425 practice questions in 17 sets of 25
    Premium
  4. 4
    Verifying an Electrically Safe Work Condition and Temporary Grounding9 key notes, 115 flashcards, then 425 practice questions in 17 sets of 25
    Premium
  5. 5
    Justifying Energized Work, Permits and Shock Risk Assessment8 key notes, 115 flashcards, then 425 practice questions in 17 sets of 25
    Premium
  6. 6
    Arc Flash Risk Assessment, Labels and PPE8 key notes, 115 flashcards, then 425 practice questions in 17 sets of 25
    Premium
  7. 7
    Special Equipment: Batteries, Lasers, Power Electronics, Laboratories, Capacitors and Cells8 key notes, 110 flashcards, then 425 practice questions in 17 sets of 25
    Premium
  8. Final step: 6 full mock exams2026 questions each, timed like test day. Pass them, then book your exam.
    Premium
Free with an account

Read the complete NFPA CESCP study notes for “Electrical Safety Program and Employer Responsibilities”

Our first full set of comprehensive notes, about 14 minutes of reading: Scope and how 70E relates to regulation · What the program must contain · Who is responsible · Documentation and proof, a worked exam example, the traps examiners use and a one-minute recap. Create a free account to read it and see how premium notes work before you decide.

Open the free dashboard

Study tools included

3,000 practice questions

3,000 exam-style questions per exam, organized topic by topic in sets of 25. Every answer explained, with the rule it comes from.

6 full mock exams

6 full-length timed mock exams per exam, with real question counts and time limits, so test day feels like practice day.

Exam Readiness Score

One 0 to 100 number that tells you when you're ready to book. Reach 80 and you're covered by our Pass Guarantee.

800 flashcards + spaced repetition

800 flashcards per exam, in a deck for each topic, that come back right before you'd forget them. Five minutes a day keeps every number fresh.

60 comprehensive key notes

60 key notes per exam, split across its topics and each explained in full: the concepts, worked exam examples, the traps examiners use and a quick recap. Your first set is free with an account.

Mind maps

See the whole exam on one screen: every topic and the facts under it.

Sample questions with answers

These are the questions in the free test above, with answers. Try the test first. You'll learn more by getting some wrong.

1. A plant hires an electrical contractor to replace a feeder. The host employer knows from a recent test that a bus section in the contractor's work area has failing insulation. The contractor does not know. What does NFPA 70E require of the host employer?
Answer: Inform the contract employer of the hazard and hold a documented meeting. Article 110 requires the host to inform contract employers of known hazards related to their work, and a documented meeting is required where the host knows of such hazards. A warning sign alone does not meet the duty. The contract employer still has its own duties to instruct its workers and report back any unique hazards.
2. After an arc flash injury, an OSHA compliance officer refers to NFPA 70E. The employer argues that 70E is a voluntary consensus standard and therefore has no bearing on the case. Which response is most accurate?
Answer: OSHA may use 70E as evidence of recognized hazards and safeguards. OSHA does not enforce NFPA 70E as a regulation, but OSHA regulations such as 29 CFR 1910 Subpart S still apply, and 70E can be evidence of what the industry recognizes as hazards and feasible safeguards. A program built only around "70E is voluntary" misses that exposure.
3. On 9 Nov 2026 a compliance professional reviews these dates: electrical safety program audit March 2024, field work audit January 2026, lockout/tagout program and procedure audit September 2025. Under NFPA 70E, which audit is overdue?
Answer: The lockout/tagout audit only. Section 110.3(L) sets maximum intervals of 3 years for the program audit and 1 year each for the field work audit and the lockout/tagout program and procedure audit. September 2025 plus 1 year has passed, while the other two are within their limits. The lockout/tagout audit must also cover at least one lockout/tagout in progress.
4. A second-year apprentice has demonstrated the ability to perform a specific voltage-measuring task safely at their level of training and works under the direct supervision of a qualified electrician. How does NFPA 70E classify the apprentice for that task?
Answer: Considered qualified for those specific duties. Article 110 treats an employee in on-the-job training as qualified for specific duties once they demonstrate the ability to do them safely and work under the direct supervision of a qualified person. The status is limited to those duties. It does not extend to other tasks or to unsupervised work.
5. An incident energy study assumes a 480 V feeder breaker clears in 0.05 second. Records show the breaker has not been exercised or tested in 12 years. What should the compliance professional conclude?
Answer: Poor maintenance could lengthen clearing time, so the label may be unsafe. The arc flash risk assessment must take into account the protective device's opening time, including its condition of maintenance. Incident energy rises with arcing time, so a slow or seized breaker can make the label unsafe. Test or maintain the breaker and then revisit the analysis; adding a PPE category by guesswork has no basis.
6. A shutdown involves electrical and instrumentation crews from two employers, three disconnecting means and work that continues across two shifts. Which lockout/tagout approach does NFPA 70E call for?
Answer: Complex lockout/tagout with a written plan and a named person in charge. Multiple crews, crafts, employers, disconnecting means and work over more than one period each make a procedure complex. Article 120 requires a complex lockout/tagout to have a written plan of execution that identifies the person in charge. Personal locks remain part of it, but they do not replace the plan.
7. An older disconnect's design makes it impossible to install a lock. A job requires an electrically safe work condition on the downstream circuit. How may the employer proceed under Article 120?
Answer: Use a tag plus an added safety measure, and not this disconnect alone. Tagout without a lock is permitted only where equipment design precludes a lock, and it needs at least one additional safety measure. A disconnect that cannot take a lock must not be the sole means of establishing the safe condition. OSHA's lockout rules point the same way. Wiring the handle is not a recognized control.
8. A crew will work at two separate points in a de-energized 480 V switchboard. The electrician tests for absence of voltage at the first point only, reasoning that the bus is common. Under the current edition, what is wrong with this?
Answer: Absence of voltage must be tested at each point of work. Section 120.6 in the current edition requires testing each phase conductor or circuit part at each point of work, phase-to-phase and phase-to-ground. The tester must also be verified on a known source before and after the test. Assuming a common bus is exactly the error this added wording addresses.
9. During a 13.8 kV outage, conductors could reasonably contact another energized circuit. Available fault current is 25 kA with a 0.5-second clearing time. On what basis should temporary protective grounding equipment be selected?
Answer: The fault current possible at that point, for the time to clear it. Temporary protective grounding equipment must be able to conduct the maximum fault current that could flow at the point of grounding for the time needed to clear the fault, and must be placed to protect each employee. Sizing it on load current or phase conductor size ignores the fault duty it must survive.
10. A plant manager wants a contactor in a 480 V motor control center replaced energized because a shutdown costs US$80,000 an hour. The line can be stopped, and stopping it creates no other hazard. Is energized work justified under NFPA 70E?
Answer: No, because cost alone is neither added hazard nor infeasibility. Energized work is allowed only where de-energizing introduces additional hazards or increased risk, or where the task is infeasible de-energized because of equipment design or operational limitations. Lost production is neither. A signed permit documents a justified decision, but it cannot create the justification.
11. Which task, performed by a qualified person within the limited approach boundary of a 480 V panelboard, requires an energized electrical work permit under the current edition?
Answer: Installing a bolt-on breaker in the energized panelboard. Section 130.2 requires a permit for work within the restricted approach boundary. The listed exemptions include testing, troubleshooting and voltage measuring, and thermography and housekeeping where the restricted approach boundary is not crossed. Installing a breaker is none of these. Exempt tasks still need safe practices and PPE.
12. An incident energy analysis shows 11.6 cal/cm2 at the working distance. A supervisor selects PPE Category 3 from Table 130.7(C)(15)(c) because its 25 cal/cm2 minimum looks conservative. What is the correct finding?
Answer: Not acceptable: use Table 130.5(G) at 11.6 cal/cm2 or higher. The two arc flash PPE methods cannot both be used on the same equipment, and incident energy results may not be used to specify a PPE category from the table. Select arc-rated clothing with Table 130.5(G) at or above the calculated energy. Higher category PPE also brings needless heat and restricted movement.
13. A 600-volt class motor control center has 40 kA available fault current and a 0.5-second fault clearing time. Can the arc flash PPE category method be used?
Answer: No, because clearing time exceeds the table limits for this equipment. Table 130.7(C)(15)(a) lists motor control centers only within set parameters: up to 65 kA at 0.03 second (Category 2), or up to 42 kA at 0.33 second (Category 4). At 0.5 second both are exceeded, and equipment outside the parameters needs an incident energy analysis. Checking only the fault current is the common error.
14. During a program audit, a switchboard label shows nominal voltage, arc flash boundary, incident energy of 9.2 cal/cm2 at 18 in., and also PPE Category 3. What is the audit finding?
Answer: Not compliant: incident energy and a PPE category cannot both appear. Section 130.5(H) requires nominal voltage, the arc flash boundary and at least one of the listed hazard or PPE entries, but incident energy and PPE category may not both be shown. Showing both invites the method mixing the standard forbids. Labels must also be reviewed at intervals not exceeding 5 years.
15. A stationary 48 V battery system has 1,200 A of available short-circuit current at its terminals. A supervisor says Article 320 does not apply because the system is under 100 V. Is the supervisor correct under the current edition?
Answer: No: short-circuit power is about 28.8 kW, above the 1,000 W threshold. Article 320 covers exposed stationary batteries over 100 V or over 1,000 W of short-circuit power. Short-circuit power is voltage times available short-circuit current divided by 2: 48 x 1,200 / 2 = 28,800 W. A low-voltage battery can still carry a serious thermal hazard, so a risk assessment is required before work.

Get the full NFPA CESCP prep

Most popular · cancel anytime

Premium Monthly

$147/month
per exam
About $4.83 a day · less than a single code book, for a certification employers and AHJs ask for by name
  • One NFPA exam of your choice: CFPS, CFI or CFPE
  • 3,000 practice questions + 6 full mock exams per exam
  • 800 flashcards + 60 key notes per exam, by topic, plus mind maps
  • Spaced repetition + mistakes bank
  • Readiness Score & detailed reports
  • Video lessons as they release
  • Content updates during your access
  • 5 bonuses: formulas and values sheet, code values quick reference, study planner and more
  • Pass Guarantee: complete the prep, pass or 100% back

Renews monthly until you cancel. Cancel in two clicks from your account; you keep access until the end of the month you've paid for. No minimum term.

Best value · 3 months free

Premium Yearly

$1,323/year
per exam
Pay for 9 months, get 12. Save $441 against paying monthly.
  • One NFPA exam of your choice: CFPS, CFI or CFPE
  • 3,000 practice questions + 6 full mock exams per exam
  • 800 flashcards + 60 key notes per exam, by topic, plus mind maps
  • Spaced repetition + mistakes bank
  • Readiness Score & detailed reports
  • Video lessons as they release
  • Content updates during your access
  • 5 bonuses: formulas and values sheet, code values quick reference, study planner and more
  • Pass Guarantee: complete the prep, pass or 100% back

Renews once a year until you cancel. We email you before each renewal. Cancel any time from your account; you keep access until the end of the year you've paid for.

Pass Guarantee. Complete the full prep, sit your exam within 60 days, and if you don't pass we refund 100% of your subscription payments. See the requirements
Secure checkout by Stripe Card, Apple Pay, Google Pay Pass Guarantee

NFPA CESCP exam FAQ

How many questions are on the NFPA CESCP exam?

NFPA's sources differ: the CESCP Program Overview 2026 says 110 multiple-choice questions (100 scored, 10 unscored), while NFPA's CESCP web page says 86. Confirm with NFPA before test day, with a time limit of 3 hours. Format: open book: only the official printed nfpa 70e, standard for electrical safety in the workplace, in the edition named by the exam body. the nfpa 70e handbook is for preparation only and is not allowed in the exam.

What is the passing score for NFPA CESCP?

Not published by NFPA: results are reported as pass or fail with a diagnostic report, and the score is not disclosed. Aim for 75% or higher in practice.

How much does the NFPA CESCP exam cost?

US$499 initial application and exam; US$249 retest; US$225 recertification every 3 years. Fees and reference editions change, so confirm on nfpa.org before you apply.

Which languages is the NFPA CESCP exam offered in?

English only.

Where do I take the NFPA CESCP exam?

Prometric (in-person computer-based test centers worldwide).

Is this NFPA CESCP practice test free?

Yes. The 15-question practice test on this page is free, with an explanation for every answer and no signup. A free account also unlocks the complete study notes for the first topic. The full NFPA CESCP prep is Premium at $147 a month for this exam.

What's in the premium NFPA CESCP prep?

3,000 practice questions organized topic by topic (Electrical Safety Program and Employer Responsibilities: 450; Risk Assessment, Training, Audits and Maintenance: 425; Lockout/Tagout Program and Procedures: 425; Verifying an Electrically Safe Work Condition and Temporary Grounding: 425; Justifying Energized Work, Permits and Shock Risk Assessment: 425; Arc Flash Risk Assessment, Labels and PPE: 425; Special Equipment: Batteries, Lasers, Power Electronics, Laboratories, Capacitors and Cells: 425), 6 full-length timed mock exams of 2026 questions, 800 flashcards and 60 comprehensive key notes split across all 7 topics, plus a mistakes bank and the Readiness Score.