Try the full study dashboard free, no signup: practice, flashcards and your Exam Readiness Score. Open it →
NFPA · Last updated November 2026

Certified Electrical Safety Technician (CEST): free practice test

NFPA's credential for workers who are exposed to electrical hazards but are not necessarily electricians, based on NFPA 70E. The exam weights are Electrical Safety Programs 15%, Electrical Safety-Related Work Practices 45%, Electrical Hazard Risk Assessments 30% and Work Involving Electrical Hazards 10%.

Watch the free 4:40 video lesson: the key CEST concepts →

Premium: 3,000 practice questions, 6 full mock exams, 800 flashcards and 60 comprehensive key notes, topic by topic. See the study path ·

Or open the free CEST study dashboard: flashcards, notes and your Readiness Score, no signup →

About the CEST exam

NFPA's credential for workers who are exposed to electrical hazards but are not necessarily electricians, based on NFPA 70E. The exam weights are Electrical Safety Programs 15%, Electrical Safety-Related Work Practices 45%, Electrical Hazard Risk Assessments 30% and Work Involving Electrical Hazards 10%.

What's on the exam

CEST
Electrical Safety Programs and Training
7 key facts
Definitions, General Practices and Emergency Response
8 key facts
Job Planning, Lockout/Tagout and Electrically Safe Work
8 key facts
Test Instruments, GFCI and Other Protective Measures
8 key facts
Electrical Hazards and Shock Risk Assessment
7 key facts
Arc Flash Risk Assessment
7 key facts
PPE for Electrical Hazards
7 key facts
Energized Work and Permits
6 key facts

Each branch is a topic in the official outline. Members see every key fact on the full mind map. Read the free study guide →

How to pass the CEST exam

  • Work Practices is 45% of the exam, so learn the steps in 120.5 and the lockout/tagout rules in Article 120 until you can find them in seconds.
  • Bring only the edition currently listed by the exam body. Section numbers move between editions, and the printed standard in that edition is the only book allowed in the room.
  • Tab Table 130.4(E)(a), Table 130.5(G), Table 130.7(C)(15)(a) and Table 130.7(C)(15)(c) with permanent tabs before exam day. You cannot add tabs during the exam.
  • With 110 questions in 3 hours you have about 98 seconds each. Answer what you know first, then use the book for look-up questions.

Save your results and get your Readiness Score

Create a free account after the test: your score by topic, a mistakes bank, the complete study notes for the first topic, flashcards and the Fire Protection Formulas & Values Sheet.

Take the test first

What's in the premium CEST prep

Premium CEST prep is studied one topic at a time. Each step starts with that topic's key notes and flashcard deck, then its own question sets of 25, so you master one topic before you move to the next. When every topic is strong, the 6 full mock exams show you're ready.

3,000practice questions, every answer explained
6full-length mock exams, 110 questions each, timed
800flashcards with spaced repetition, sorted by topic
60comprehensive key notes across 8 topics

Your step-by-step study path

  1. 1
    Electrical Safety Programs and Training8 key notes, 100 flashcards, then 375 practice questions in 15 sets of 25
    Notes free with an account
  2. 2
    Definitions, General Practices and Emergency Response8 key notes, 100 flashcards, then 375 practice questions in 15 sets of 25
    Premium
  3. 3
    Job Planning, Lockout/Tagout and Electrically Safe Work8 key notes, 100 flashcards, then 375 practice questions in 15 sets of 25
    Premium
  4. 4
    Test Instruments, GFCI and Other Protective Measures8 key notes, 100 flashcards, then 375 practice questions in 15 sets of 25
    Premium
  5. 5
    Electrical Hazards and Shock Risk Assessment7 key notes, 100 flashcards, then 375 practice questions in 15 sets of 25
    Premium
  6. 6
    Arc Flash Risk Assessment7 key notes, 100 flashcards, then 375 practice questions in 15 sets of 25
    Premium
  7. 7
    PPE for Electrical Hazards7 key notes, 100 flashcards, then 375 practice questions in 15 sets of 25
    Premium
  8. 8
    Energized Work and Permits7 key notes, 100 flashcards, then 375 practice questions in 15 sets of 25
    Premium
  9. Final step: 6 full mock exams110 questions each, timed like test day. Pass them, then book your exam.
    Premium
Free with an account

Read the complete CEST study notes for “Electrical Safety Programs and Training”

Our first full set of comprehensive notes, about 12 minutes of reading: The electrical safety program · Risk assessment and the hierarchy of controls · Qualified and unqualified persons · Training and retraining · Worker responsibilities, a worked exam example, the traps examiners use and a one-minute recap. Create a free account to read it and see how premium notes work before you decide.

Open the free dashboard

Study tools included

3,000 practice questions

3,000 exam-style questions per exam, organized topic by topic in sets of 25. Every answer explained, with the rule it comes from.

6 full mock exams

6 full-length timed mock exams per exam, with real question counts and time limits, so test day feels like practice day.

Exam Readiness Score

One 0 to 100 number that tells you when you're ready to book. Reach 80 and you're covered by our Pass Guarantee.

800 flashcards + spaced repetition

800 flashcards per exam, in a deck for each topic, that come back right before you'd forget them. Five minutes a day keeps every number fresh.

60 comprehensive key notes

60 key notes per exam, split across its topics and each explained in full: the concepts, worked exam examples, the traps examiners use and a quick recap. Your first set is free with an account.

Mind maps

See the whole exam on one screen: every topic and the facts under it.

Sample questions with answers

These are the questions in the free test above, with answers. Try the test first. You'll learn more by getting some wrong.

1. An HVAC technician completed documented NFPA 70E work-practice training 38 months ago. The job has not changed and field audits found no problems. Under the current edition, what is the status of the technician's training?
Answer: Retraining is overdue, because the interval must not exceed 3 years. Article 110 sets retraining at intervals not exceeding 3 years, even when nothing about the job has changed. Changed duties, new technology or failed audits can bring retraining forward, but they never extend the limit. The 5-year figure belongs to the arc flash risk assessment review.
2. A plant fits infrared viewing windows to a 480 V switchboard so thermographic scans can be done with the doors closed. In the hierarchy of risk control methods, this measure is best classified as:
Answer: Engineering controls. The energized parts are still there, so the hazard has not been eliminated. The windows physically separate the worker from the exposure, which is what an engineering control does. Awareness covers warnings and labels, and administrative controls are procedures and training. Learn the order: elimination, substitution, engineering controls, awareness, administrative controls, PPE.
3. A facilities technician needs to reach a terminal behind a bundle of wiring in a dark control cabinet. Nearby parts are energized at 277 V and the terminal cannot be seen. What should happen first?
Answer: Stop and add lighting or reposition so the path of the hand can be seen. Section 130.6 prohibits reaching blindly into areas that might contain exposed energized parts and requires adequate illumination before entering such spaces. Leather gloves are not shock protection, and an observer at the door cannot see where the hand is going. If you cannot see it, you do not reach for it.
4. A maintenance crew exposed to shock hazards completed contact-release training 15 months ago. Their CPR cards remain valid for 6 more months. Under 110.6, which item needs action now?
Answer: The contact-release refresher, which must occur annually. Employees exposed to shock hazards, and those responsible for releasing victims, need contact-release refresher training annually. CPR and AED training follows the certifying body's frequency, so a card still in date is fine. The 3-year limit applies to general work-practice retraining, and a CPR card does not cover release methods.
5. Partway through a job on a de-energized lighting panel, the crew finds a second feeder from an emergency panel that was not in the job safety plan. What is required?
Answer: Repeat job safety planning and the job briefing before continuing the work. Job safety planning and the job briefing must be repeated when changes that might affect safety occur during the work. The new source also has to be included when establishing the electrically safe work condition, so finishing first is not an option. A lock applied by one person while the others carry on skips the required replanning.
6. Which order follows the 120.5 process for establishing an electrically safe work condition?
Answer: Identify sources, interrupt load and open disconnects, release stored energy, apply lockout/tagout, test for absence of voltage. 120.5 begins with finding every possible source from up-to-date drawings and tags. You then interrupt load current, open the disconnects, release stored energy, apply lockout/tagout devices and test for absence of voltage. Testing comes after the locks go on, because the equipment is not safe until absence of voltage is proven.
7. A technician working alone de-energizes one 208 V disconnect to replace a motor within a single shift, and the employer classifies this as a simple lockout/tagout. What applies?
Answer: No written plan is needed for this application, and the technician applies their own lock. A simple lockout/tagout involves qualified persons de-energizing one set of conductors or circuit parts for employee protection. No written plan is required for each application, and each worker is responsible for their own lockout/tagout. A written plan with a person in charge is the mark of a complex procedure.
8. A technician plans to verify absence of voltage at a 480 V distribution panel using a meter rated CAT II 300 V. What does NFPA 70E require?
Answer: Use an instrument rated for this 480 V circuit and location, which this meter is not. Test instruments, equipment and accessories must be rated for the circuits and equipment where they are used; the informational note points to the ANSI/UL 61010 categories. A CAT II 300 V meter is not rated for a 480 V distribution panel. Checking on a known source proves it works, not that it is rated, and PPE does not fix an under-rated instrument.
9. During energized troubleshooting of 480 V equipment in a busy corridor, signs and barricades are in place at the limited approach boundary, but staff keep walking through. What should be added?
Answer: An attendant to keep unqualified people outside the work area. Under 130.7(E), when signs and barricades do not give sufficient warning and protection, an attendant must be stationed to keep unqualified people out. More signs repeat the measure that has already failed. Conductive barricades must not be used where they could create an electrical hazard.
10. Temporary flexible cables energized at 480 V are strung across a work area. Using Table 130.4(E)(a), what is the limited approach boundary for these conductors?
Answer: 10 ft 0 in.. Flexible, unsecured cables are treated as exposed movable conductors, so the limited approach boundary at this voltage is 10 ft 0 in. The 3 ft 6 in. value is for fixed circuit parts in the same voltage range, and 1 ft 0 in. is the restricted approach boundary. Check whether the conductor can move before you read the table.
11. A qualified electrician must cross the restricted approach boundary of exposed 480 V parts to perform permitted energized work. Which condition allows this?
Answer: Rubber insulating gloves and sleeves, so no uninsulated body part crosses. A qualified person may cross the restricted approach boundary only when insulated or guarded from the energized parts so no uninsulated body part crosses it, or when the parts are insulated from the person. Arc-rated clothing protects against thermal energy, not shock. Permits and observers are controls on the work, not shock protection.
12. After a utility change, available fault current at a fused 480 V panel falls from 30 kA to 12 kA. The study shows the fuse now clears in 0.5 second instead of 0.03 second. What should be expected?
Answer: Incident energy rises, because the longer clearing time outweighs the lower current. Incident energy depends on both arcing current and duration. Dropping the fault current can take a fuse out of its current-limiting range, so clearing time here rises about 16 times while current falls only 2.5 times, and energy goes up. That is why an arc flash assessment must be updated when the system changes.
13. A panel label shows an arc flash boundary of 52 in. and 6 cal/cm2 at 18 in. A second qualified technician will hold a light 36 in. from the open door during the job. What applies to the second technician?
Answer: PPE is needed, because the technician is inside the arc flash boundary. The arc flash boundary is where incident energy falls to 1.2 cal/cm2, so anyone inside it needs protection based on the energy at their position. The 6 cal/cm2 value applies only at 18 in., and at 36 in. the exposure is lower but still above 1.2. Restricted approach boundaries govern shock, not arc flash.
14. An incident energy analysis gives 6.5 cal/cm2 at the working distance, and the label lists no PPE. Using Table 130.5(G), which selection for body and face is correct?
Answer: Arc-rated clothing and a face shield with balaclava, rated at least 6.5 cal/cm2. When incident energy is known, select PPE from Table 130.5(G) with an arc rating at or above the calculated value; from 1.2 to 12 cal/cm2 that includes an arc-rated face shield with balaclava or an arc flash suit hood. PPE Category 1 is only 4 cal/cm2, and categories are not used alongside an incident energy result. Non-melting natural fiber is for exposures below 1.2 cal/cm2.
15. Which job gives an acceptable basis for energized work under section 110.4?
Answer: Tracing an intermittent control fault that appears only while energized. 110.4 permits energized work where de-energizing creates additional hazards or increased risk, or where it is infeasible, such as diagnostics that can be done only with the circuit energized. Tracing a fault that appears only when powered fits that. Convenience, schedule pressure and tenant disruption are not acceptable justifications.

Get the full CEST prep

Most popular · cancel anytime

Premium Monthly

$147/month
per exam
About $4.83 a day · less than a single code book, for a certification employers and AHJs ask for by name
  • One NFPA exam of your choice: CFPS, CFI or CFPE
  • 3,000 practice questions + 6 full mock exams per exam
  • 800 flashcards + 60 key notes per exam, by topic, plus mind maps
  • Spaced repetition + mistakes bank
  • Readiness Score & detailed reports
  • Video lessons as they release
  • Content updates during your access
  • 5 bonuses: formulas and values sheet, code values quick reference, study planner and more
  • Pass Guarantee: complete the prep, pass or 100% back

Renews monthly until you cancel. Cancel in two clicks from your account; you keep access until the end of the month you've paid for. No minimum term.

Best value · 3 months free

Premium Yearly

$1,323/year
per exam
Pay for 9 months, get 12. Save $441 against paying monthly.
  • One NFPA exam of your choice: CFPS, CFI or CFPE
  • 3,000 practice questions + 6 full mock exams per exam
  • 800 flashcards + 60 key notes per exam, by topic, plus mind maps
  • Spaced repetition + mistakes bank
  • Readiness Score & detailed reports
  • Video lessons as they release
  • Content updates during your access
  • 5 bonuses: formulas and values sheet, code values quick reference, study planner and more
  • Pass Guarantee: complete the prep, pass or 100% back

Renews once a year until you cancel. We email you before each renewal. Cancel any time from your account; you keep access until the end of the year you've paid for.

Pass Guarantee. Complete the full prep, sit your exam within 60 days, and if you don't pass we refund 100% of your subscription payments. See the requirements
Secure checkout by Stripe Card, Apple Pay, Google Pay Pass Guarantee

CEST exam FAQ

How many questions are on the CEST exam?

110 multiple-choice questions (100 scored, 10 unscored test items), with a time limit of 3 hours maximum. Format: open book: the official printed nfpa 70e, standard for electrical safety in the workplace, in the edition named by the exam body, is the only reference allowed. the nfpa 70e handbook may be used to study but not in the exam. permanent tabs only, added before the exam; personal calculators are not permitted, and a calculator is on screen. nfpa may issue later 70e editions with changed section numbers, so study from the edition currently listed by the exam body.

What is the passing score for CEST?

Not published by NFPA; results are reported as pass or fail only, with a diagnostic report by content area.

How much does the CEST exam cost?

US$499 initial application and exam; US$249 retest; US$225 recertification every 3 years. Fees and reference editions change, so confirm on nfpa.org before you apply.

Which languages is the CEST exam offered in?

English only.

Where do I take the CEST exam?

Prometric (proctored computer-based exam at in-person test centers worldwide).

Is this CEST practice test free?

Yes. The 15-question practice test on this page is free, with an explanation for every answer and no signup. A free account also unlocks the complete study notes for the first topic. The full CEST prep is Premium at $147 a month for this exam.

What's in the premium CEST prep?

3,000 practice questions organized topic by topic (Electrical Safety Programs and Training: 375; Definitions, General Practices and Emergency Response: 375; Job Planning, Lockout/Tagout and Electrically Safe Work: 375; Test Instruments, GFCI and Other Protective Measures: 375; Electrical Hazards and Shock Risk Assessment: 375; Arc Flash Risk Assessment: 375; PPE for Electrical Hazards: 375; Energized Work and Permits: 375), 6 full-length timed mock exams of 110 questions, 800 flashcards and 60 comprehensive key notes split across all 8 topics, plus a mistakes bank and the Readiness Score.

Related practice tests

Exam details are summarized from the official candidate information available in November 2026. NFPA changes formats and fees, so confirm with National Fire Protection Association (NFPA) before you book. CFPSExamPrep is not affiliated with NFPA or Prometric.

Start the free test