ICC Commercial Fire Sprinkler Plans Examiner (CP): free practice test

ICC's certification for plans examiners who decide whether commercial fire sprinkler, standpipe and fire pump submittals meet the adopted codes and NFPA standards. Hydraulic calculations and water supply are 31% of the exam, standpipes and materials 11% each, and the rest covers plan reading, use group and hazard classification, fire pumps, storage, FDCs, seismic bracing and freeze protection.

Watch the free 4:19 video lesson: the key ICC Sprinkler Plans Examiner (CP) concepts →

Premium: 3,000 practice questions, 6 full mock exams, 800 flashcards and 60 comprehensive key notes, topic by topic. See the study path ·

Or open the free ICC Sprinkler Plans Examiner (CP) study dashboard: flashcards, notes and your Readiness Score, no signup →

About the ICC Sprinkler Plans Examiner (CP) exam

ICC's certification for plans examiners who decide whether commercial fire sprinkler, standpipe and fire pump submittals meet the adopted codes and NFPA standards. Hydraulic calculations and water supply are 31% of the exam, standpipes and materials 11% each, and the rest covers plan reading, use group and hazard classification, fire pumps, storage, FDCs, seismic bracing and freeze protection.

What's on the exam

ICC Sprinkler Plans Examiner (CP)
Hydraulic Calculations and Water Supply
8 key facts
Plans, Use Group, Construction and Hazard Classification
7 key facts
Standpipes
7 key facts
Materials and System Components
7 key facts
Fire Pumps
7 key facts
Commodities and Storage
7 key facts
Fire Department Connections, Seismic and Freeze Protection
6 key facts

Each branch is a topic in the official outline. Members see every key fact on the full mind map. Read the free study guide →

How to pass the ICC Sprinkler Plans Examiner (CP) exam

  • 75 questions in 150 minutes is 2 minutes each. Do the hydraulic and K-factor arithmetic on scratch paper first, then confirm the table value in NFPA 13.
  • Hydraulic calculations and water supply are 31% of the exam. Tab the density/area curves, the hose stream allowance table, the C-factor table and the equivalent pipe length table.
  • Four NFPA standards beyond NFPA 13 are on the list: know where standpipe flow and pressure (NFPA 14), pump acceptance and room rules (NFPA 20), and private mains and tanks (NFPA 24 and 22) live.
  • Use the same editions ICC lists. NFPA 13 has been reorganized between editions, so a different edition sends you to the wrong chapter under time pressure.

Save your results and get your Readiness Score

Create a free account after the test: your score by topic, a mistakes bank, the complete study notes for the first topic, flashcards and the Fire Protection Formulas & Values Sheet.

Take the test first

What's in the premium ICC Sprinkler Plans Examiner (CP) prep

Premium ICC Sprinkler Plans Examiner (CP) prep is studied one topic at a time. Each step starts with that topic's key notes and flashcard deck, then its own question sets of 25, so you master one topic before you move to the next. When every topic is strong, the 6 full mock exams show you're ready.

3,000practice questions, every answer explained
6full-length mock exams, 75 questions each, timed
800flashcards with spaced repetition, sorted by topic
60comprehensive key notes across 7 topics

Your step-by-step study path

  1. 1
    Hydraulic Calculations and Water Supply9 key notes, 115 flashcards, then 450 practice questions in 18 sets of 25
    Notes free with an account
  2. 2
    Plans, Use Group, Construction and Hazard Classification9 key notes, 115 flashcards, then 425 practice questions in 17 sets of 25
    Premium
  3. 3
    Standpipes9 key notes, 115 flashcards, then 425 practice questions in 17 sets of 25
    Premium
  4. 4
    Materials and System Components9 key notes, 115 flashcards, then 425 practice questions in 17 sets of 25
    Premium
  5. 5
    Fire Pumps8 key notes, 115 flashcards, then 425 practice questions in 17 sets of 25
    Premium
  6. 6
    Commodities and Storage8 key notes, 115 flashcards, then 425 practice questions in 17 sets of 25
    Premium
  7. 7
    Fire Department Connections, Seismic and Freeze Protection8 key notes, 110 flashcards, then 425 practice questions in 17 sets of 25
    Premium
  8. Final step: 6 full mock exams75 questions each, timed like test day. Pass them, then book your exam.
    Premium
Free with an account

Read the complete ICC Sprinkler Plans Examiner (CP) study notes for “Hydraulic Calculations and Water Supply”

Our first full set of comprehensive notes, about 16 minutes of reading: Water supply data · Design area and density · Sprinkler and pipe inputs · Hose stream allowance and the final check, a worked exam example, the traps examiners use and a one-minute recap. Create a free account to read it and see how premium notes work before you decide.

Open the free dashboard

Study tools included

3,000 practice questions

3,000 exam-style questions per exam, organized topic by topic in sets of 25. Every answer explained, with the rule it comes from.

6 full mock exams

6 full-length timed mock exams per exam, with real question counts and time limits, so test day feels like practice day.

Exam Readiness Score

One 0 to 100 number that tells you when you're ready to book. Reach 80 and you're covered by our Pass Guarantee.

800 flashcards + spaced repetition

800 flashcards per exam, in a deck for each topic, that come back right before you'd forget them. Five minutes a day keeps every number fresh.

60 comprehensive key notes

60 key notes per exam, split across its topics and each explained in full: the concepts, worked exam examples, the traps examiners use and a quick recap. Your first set is free with an account.

Mind maps

See the whole exam on one screen: every topic and the facts under it.

Sample questions with answers

These are the questions in the free test above, with answers. Try the test first. You'll learn more by getting some wrong.

1. A wet pipe system uses K5.6 sprinklers, each covering 130 sq ft, with a design density of 0.20 gpm/sq ft. What pressure is required at the most remote sprinkler to deliver the density?
Answer: About 21.6 psi. Flow is density times area: 0.20 x 130 = 26 gpm. From Q = K x square root of P, P = (26 / 5.6) squared = 21.6 psi. Forgetting to square gives 4.6 psi, and 7 psi is only a floor that applies when the calculated pressure is lower.
2. An Ordinary Hazard Group 2 area will be protected by a dry pipe system using the density/area method at 0.20 gpm/sq ft over 1,500 sq ft. What design area should the hydraulic calculation use?
Answer: 1,950 sq ft. NFPA 13 requires the density/area design area to be increased by 30% for dry pipe and double-interlock preaction systems, with no change to the density: 1,500 x 1.3 = 1,950 sq ft. The increase compensates for the delay before water reaches the open sprinklers.
3. A flow test shows 70 psi static and 50 psi residual while flowing 1,000 gpm. Using the N^1.85 relationship, about what pressure is available from this supply at 500 gpm?
Answer: 64.5 psi. Pressure drop varies with flow to the 1.85 power: 70 - 20 x (500/1,000)^1.85 = 70 - 20 x 0.277 = 64.5 psi. Straight-line interpolation gives 60 psi and understates the supply, which is why water supply curves are drawn on N^1.85 graph paper.
4. An Ordinary Hazard Group 2 system calculates to 410 gpm at the base of the riser. What total water demand should the reviewer check against the water supply?
Answer: 660 gpm. NFPA 13 adds a combined inside and outside hose stream allowance of 250 gpm for ordinary hazard occupancies, for a 60 to 90 minute duration: 410 + 250 = 660 gpm. Light hazard adds 100 gpm and extra hazard 500 gpm.
5. Sprinkler shop drawings for a new hardware and home goods store classify the sales floor as Light Hazard. How should the plans examiner respond?
Answer: Require at least Ordinary Hazard Group 2. NFPA 13's annex lists mercantile occupancies as Ordinary Hazard Group 2 because of their high combustible loading and display heights. Quick-response sprinklers reduce the design area but do not change the hazard classification, and storage over 12 ft would need storage criteria.
6. A proposed one-story Group M store has a single fire area of 13,500 sq ft and no upholstered furniture or mattresses. Under the IFC, does it need an automatic sprinkler system?
Answer: Yes, because the fire area exceeds 12,000 sq ft. IFC Section 903.2.7 requires sprinklers in Group M where a fire area exceeds 12,000 sq ft. The 24,000 sq ft figure is the combined area of all Group M fire areas on all floors, and 3 stories above grade plane is a separate, independent trigger.
7. A fully sprinklered high-rise has three Class I standpipes. What minimum flow should the standpipe hydraulic calculation show under NFPA 14?
Answer: 1,000 gpm. NFPA 14 requires 500 gpm for the most remote standpipe plus 250 gpm for each additional standpipe: 500 + 250 + 250 = 1,000 gpm. The total need not exceed 1,000 gpm in a fully sprinklered building (1,250 gpm otherwise), with 100 psi residual at the most remote 2.5-in. outlet.
8. The calculation for a tall building shows a static pressure of 190 psi at a lower-floor 2.5-in. hose connection used by the fire department. What does NFPA 14 require?
Answer: A device limiting static and residual pressure to 175 psi. Where static pressure at a hose connection exceeds 175 psi, NFPA 14 requires a pressure-regulating device that limits static and residual pressure to 175 psi at 2.5-in. connections (100 psi at 1.5-in. connections for trained personnel). The 350 psi figure is a system component limit, not an outlet limit.
9. Plans show sprinklers in an unventilated attic where ceiling temperatures can reach 140°F. Which sprinkler temperature classification is required?
Answer: Intermediate (175°F to 225°F). NFPA 13 links each temperature classification to a maximum ceiling temperature: ordinary 100°F, intermediate 150°F, high 225°F. A 140°F ceiling exceeds the ordinary limit but is within intermediate, so intermediate sprinklers are needed to avoid premature operation.
10. Shop drawings show 1-in. Schedule 40 steel branch lines with hangers spaced 14 ft apart. What should the plans examiner conclude?
Answer: Noncompliant, as 1-in. steel pipe needs hangers at 12 ft. NFPA 13's maximum hanger spacing table allows 12 ft for 1-in. steel pipe and 15 ft for 1.25-in. and larger steel pipe. Plastic pipe such as CPVC has much shorter spacings that come from its listing, so check the pipe material before applying the table.
11. A fire pump is rated at 750 gpm and 100 psi. During plan review of the pump curve, what minimum net pressure must the pump produce at 1,125 gpm?
Answer: 65 psi. NFPA 20 requires a centrifugal pump to deliver at least 150% of rated flow (1,125 gpm) at not less than 65% of rated net pressure, so 65 psi. Shutoff (churn) pressure must not exceed 140% of rated pressure, which is where the 140 psi figure comes from.
12. A fire pump is proposed in a four-story office building (not a high-rise) that is sprinklered throughout. What minimum separation must the pump room have under the IFC and IBC?
Answer: 1-hour fire barriers or horizontal assemblies. Fire pump rooms need 2-hour fire barriers or horizontal assemblies, but an exception allows 1-hour separation in buildings sprinklered throughout that are not high-rises. In a high-rise the 2-hour separation applies regardless of sprinklers.
13. A warehouse owner's certificate lists noncombustible metal parts packed in multiple-layer corrugated cartons on wood pallets. What commodity class should the review use?
Answer: Class II. Under NFPA 13, noncombustible products on wood pallets or in single-layer corrugated cartons are Class I. Packing them in multiple-layer corrugated cartons, slatted wooden crates or solid wood boxes makes them Class II. Class III and IV involve combustible products or plastics.
14. Seismic bracing details show a 4-in. feed main with longitudinal sway braces spaced 100 ft apart. What should the plans examiner require?
Answer: Longitudinal braces no more than 80 ft apart. NFPA 13 limits longitudinal sway bracing on feed and cross mains to 80 ft apart, while lateral braces are limited to 40 ft (less where the load table requires). Four-way bracing is required at the top of risers, in addition to the line bracing.
15. A sprinkler riser detail shows an indicating control valve in the fire department connection piping, between the FDC check valve and the system. What should the plans examiner do?
Answer: Require removal of the shutoff valve. NFPA 13 does not allow a shutoff valve in the FDC piping, because a closed valve would silently defeat fire department pumping into the system. The FDC line needs a listed check valve, and a ball drip at the low point, not a control valve.

Get the full ICC Sprinkler Plans Examiner (CP) prep

Most popular · cancel anytime

Premium Monthly

$147/month
per exam
About $4.83 a day · less than a single code book, for a certification employers and AHJs ask for by name
  • One NFPA exam of your choice: CFPS, CFI or CFPE
  • 3,000 practice questions + 6 full mock exams per exam
  • 800 flashcards + 60 key notes per exam, by topic, plus mind maps
  • Spaced repetition + mistakes bank
  • Readiness Score & detailed reports
  • Video lessons as they release
  • Content updates during your access
  • 5 bonuses: formulas and values sheet, code values quick reference, study planner and more
  • Pass Guarantee: complete the prep, pass or 100% back

Renews monthly until you cancel. Cancel in two clicks from your account; you keep access until the end of the month you've paid for. No minimum term.

Best value · 3 months free

Premium Yearly

$1,323/year
per exam
Pay for 9 months, get 12. Save $441 against paying monthly.
  • One NFPA exam of your choice: CFPS, CFI or CFPE
  • 3,000 practice questions + 6 full mock exams per exam
  • 800 flashcards + 60 key notes per exam, by topic, plus mind maps
  • Spaced repetition + mistakes bank
  • Readiness Score & detailed reports
  • Video lessons as they release
  • Content updates during your access
  • 5 bonuses: formulas and values sheet, code values quick reference, study planner and more
  • Pass Guarantee: complete the prep, pass or 100% back

Renews once a year until you cancel. We email you before each renewal. Cancel any time from your account; you keep access until the end of the year you've paid for.

Pass Guarantee. Complete the full prep, sit your exam within 60 days, and if you don't pass we refund 100% of your subscription payments. See the requirements
Secure checkout by Stripe Card, Apple Pay, Google Pay Pass Guarantee

ICC Sprinkler Plans Examiner (CP) exam FAQ

How many questions are on the ICC Sprinkler Plans Examiner (CP) exam?

75 multiple-choice questions, with a time limit of 2.5 hours. Format: open book. icc's catalog lists the ifc (also provided as a free digital reference during the exam), nfpa 13 and nfpa 13r, plus nfpa 14, nfpa 20, nfpa 22 and nfpa 24. bound, copyrighted books are allowed; study guides and practice questions are not. a version based on a newer edition is also offered: confirm its reference list in the icc catalog before buying books.

What is the passing score for ICC Sprinkler Plans Examiner (CP)?

Scaled score of 75 (ICC national certification standard); ICC does not publish the raw percentage, which varies by exam form.

How much does the ICC Sprinkler Plans Examiner (CP) exam cost?

US$320 (ICC catalog price for PRONTO delivery). Fees and reference editions change, so confirm on nfpa.org before you apply.

Which languages is the ICC Sprinkler Plans Examiner (CP) exam offered in?

English. ICC's catalog does not list other languages; confirm with ICC.

Where do I take the ICC Sprinkler Plans Examiner (CP) exam?

ICC PRONTO: in person at a test center or online with remote proctoring.

Is this ICC Sprinkler Plans Examiner (CP) practice test free?

Yes. The 15-question practice test on this page is free, with an explanation for every answer and no signup. A free account also unlocks the complete study notes for the first topic. The full ICC Sprinkler Plans Examiner (CP) prep is Premium at $147 a month for this exam.

What's in the premium ICC Sprinkler Plans Examiner (CP) prep?

3,000 practice questions organized topic by topic (Hydraulic Calculations and Water Supply: 450; Plans, Use Group, Construction and Hazard Classification: 425; Standpipes: 425; Materials and System Components: 425; Fire Pumps: 425; Commodities and Storage: 425; Fire Department Connections, Seismic and Freeze Protection: 425), 6 full-length timed mock exams of 75 questions, 800 flashcards and 60 comprehensive key notes split across all 7 topics, plus a mistakes bank and the Readiness Score.