Try the full study dashboard free, no signup: practice, flashcards and your Exam Readiness Score. Open it →
Home / Practice tests / NAFED FE Extinguisher Technician
NAFED · Last updated November 2026

NAFED Portable Fire Extinguisher Technician (FE): free practice test

The ICC/NAFED credential for technicians who inspect, maintain, recharge and hydrostatically test portable fire extinguishers, based on NFPA 10 and the federal hazardous materials rules for shipping. Annual maintenance (25%) and selection, placement and installation (20%) are the largest areas. Certification is valid for three years and renewals are handled by NAFED.

Watch the free 4:29 video lesson: the key NAFED FE Extinguisher Technician concepts →

Premium: 3,000 practice questions, 6 full mock exams, 800 flashcards and 60 comprehensive key notes, topic by topic. See the study path ·

Or open the free NAFED FE Extinguisher Technician study dashboard: flashcards, notes and your Readiness Score, no signup →

About the NAFED FE Extinguisher Technician exam

The ICC/NAFED credential for technicians who inspect, maintain, recharge and hydrostatically test portable fire extinguishers, based on NFPA 10 and the federal hazardous materials rules for shipping. Annual maintenance (25%) and selection, placement and installation (20%) are the largest areas. Certification is valid for three years and renewals are handled by NAFED.

What's on the exam

NAFED FE Extinguisher Technician
Annual Maintenance
8 key facts
Selection, Placement and Installation
8 key facts
Recordkeeping and Safety
7 key facts
Hydrostatic Testing
7 key facts
6-Year and Internal Maintenance
7 key facts
Recharging
7 key facts
Inspection
6 key facts

Each branch is a topic in the official outline. Members see every key fact on the full mind map. Read the free study guide →

How to pass the NAFED FE Extinguisher Technician exam

  • 100 questions in 2 hours is 72 seconds each, the tightest pace of the ICC/NAFED exams. Know the core numbers by heart and use the book only to confirm.
  • Tab the NFPA 10 tables you will use most: hydrostatic test intervals, internal examination intervals, and the Class A and Class B distribution tables.
  • The exam now uses the current edition of NFPA 10. If you learned on an earlier edition, read the changes on electronic monitoring, performance-based inspection and condemned cylinders.
  • Recordkeeping and safety is 16%, and it includes 49 CFR. Read NAFED's CFR 49 focus-area list and tab Parts 172, 173 and 180.

Save your results and get your Readiness Score

Create a free account after the test: your score by topic, a mistakes bank, the complete study notes for the first topic, flashcards and the Fire Protection Formulas & Values Sheet.

Take the test first

What's in the premium NAFED FE Extinguisher Technician prep

Premium NAFED FE Extinguisher Technician prep is studied one topic at a time. Each step starts with that topic's key notes and flashcard deck, then its own question sets of 25, so you master one topic before you move to the next. When every topic is strong, the 6 full mock exams show you're ready.

3,000practice questions, every answer explained
6full-length mock exams, 100 questions each, timed
800flashcards with spaced repetition, sorted by topic
60comprehensive key notes across 7 topics

Your step-by-step study path

  1. 1
    Annual Maintenance9 key notes, 115 flashcards, then 450 practice questions in 18 sets of 25
    Notes free with an account
  2. 2
    Selection, Placement and Installation9 key notes, 115 flashcards, then 425 practice questions in 17 sets of 25
    Premium
  3. 3
    Recordkeeping and Safety9 key notes, 115 flashcards, then 425 practice questions in 17 sets of 25
    Premium
  4. 4
    Hydrostatic Testing9 key notes, 115 flashcards, then 425 practice questions in 17 sets of 25
    Premium
  5. 5
    6-Year and Internal Maintenance8 key notes, 115 flashcards, then 425 practice questions in 17 sets of 25
    Premium
  6. 6
    Recharging8 key notes, 115 flashcards, then 425 practice questions in 17 sets of 25
    Premium
  7. 7
    Inspection8 key notes, 110 flashcards, then 425 practice questions in 17 sets of 25
    Premium
  8. Final step: 6 full mock exams100 questions each, timed like test day. Pass them, then book your exam.
    Premium
Free with an account

Read the complete NAFED FE Extinguisher Technician study notes for “Annual Maintenance”

Our first full set of comprehensive notes, about 14 minutes of reading: Identify the unit and the manual · Examine and decide what is due · Components, fill and charge · Repair, replace and mount, a worked exam example, the traps examiners use and a one-minute recap. Create a free account to read it and see how premium notes work before you decide.

Open the free dashboard

Study tools included

3,000 practice questions

3,000 exam-style questions per exam, organized topic by topic in sets of 25. Every answer explained, with the rule it comes from.

6 full mock exams

6 full-length timed mock exams per exam, with real question counts and time limits, so test day feels like practice day.

Exam Readiness Score

One 0 to 100 number that tells you when you're ready to book. Reach 80 and you're covered by our Pass Guarantee.

800 flashcards + spaced repetition

800 flashcards per exam, in a deck for each topic, that come back right before you'd forget them. Five minutes a day keeps every number fresh.

60 comprehensive key notes

60 key notes per exam, split across its topics and each explained in full: the concepts, worked exam examples, the traps examiners use and a quick recap. Your first set is free with an account.

Mind maps

See the whole exam on one screen: every topic and the facts under it.

Sample questions with answers

These are the questions in the free test above, with answers. Try the test first. You'll learn more by getting some wrong.

1. During annual maintenance of a cartridge-operated dry chemical extinguisher with a mild steel shell, what must the technician do in addition to the external examination?
Answer: Open it, examine the agent for caking or contamination, and weigh the cartridge. Cartridge-operated dry chemical units with mild steel shells need an internal examination every year: the agent is checked for caking and the cartridge is weighed against its stamped weight. Replacing the agent or discharging the unit is not required when the agent is in good condition, and the hydrostatic test is on a 12-year cycle.
2. A technician performing annual maintenance on a 15-lb carbon dioxide extinguisher finds it within its weight range. Which further check does NFPA 10 require on this extinguisher each year?
Answer: A conductivity test of the hose assembly. Carbon dioxide hose assemblies must pass a conductivity test every year, because a non-conductive hose can let static build up and shock the operator. The cylinder's hydrostatic test is on a 5-year cycle, and the horn is replaced only when damaged.
3. At annual maintenance, a stored-pressure ABC extinguisher has an intact tamper seal and no damage, but the gauge needle sits in the recharge zone. What is the correct action?
Answer: Take it out of service, find the cause of the pressure loss, and recharge it. A low gauge with an intact seal means the unit has leaked, so it must be removed from service, the leak found and corrected, and the extinguisher recharged following the manufacturer's manual. Simply adding pressure hides the leak, and a unit in the recharge zone cannot wait a month.
4. An ordinary hazard warehouse office area of 27,000 sq ft is to be protected with 4-A extinguishers. What is the minimum number needed based on floor area, before checking the 75-ft travel distance?
Answer: 5. For ordinary hazard, each unit of A rating covers 1,500 sq ft, so a 4-A covers 6,000 sq ft, which is below the 11,250 sq ft cap. 27,000 ÷ 6,000 = 4.5, rounded up to 5. Using the 11,250 sq ft cap gives 3, and using 2-A coverage gives 9; travel distance may still require more units.
5. In an extra hazard area with flammable liquids in depth under 0.25 in., the contractor selects extinguishers rated 40-B. What is the maximum travel distance to one of them?
Answer: 30 ft. NFPA 10's Class B table allows a 40-B extinguisher at a maximum of 30 ft in extra hazard, and an 80-B at 50 ft. The 75-ft distance applies to Class A protection, not Class B.
6. A wheel-less 20-lb carbon dioxide extinguisher weighs about 55 lb in total. Which wall mounting meets NFPA 10?
Answer: Top no higher than 3½ ft and bottom at least 4 in. above the floor. Extinguishers over 40 lb gross weight (except wheeled types) are mounted with the top no more than 3½ ft above the floor; those 40 lb or less may be up to 5 ft. In every case the bottom must be at least 4 in. above the floor.
7. A technician has just completed a full recharge of a stored-pressure ABC extinguisher, including internal examination. Which marking is required in addition to the maintenance tag?
Answer: A verification-of-service collar around the neck of the cylinder. After internal examination or recharge, a verification-of-service collar showing the month and year and the servicing agency goes around the neck, so anyone can see the unit was opened. A hydrostatic test label is applied only after a hydrostatic test, and stamping is for DOT cylinder requalification.
8. Charged stored-pressure extinguishers are being carried by truck to the shop for 6-year maintenance. Under 49 CFR, how are they described?
Answer: UN1044, Fire extinguishers, Division 2.2. Charged fire extinguishers are UN1044, Fire extinguishers, Division 2.2 (nonflammable, nontoxic gas), and 49 CFR 173.309 sets the conditions and exceptions for shipping them. Division 2.1 is flammable gas and 2.3 is toxic gas; using the wrong class is a shipping violation.
9. A customer has a stored-pressure dry chemical extinguisher with a stainless steel shell. What is its hydrostatic test interval?
Answer: 5 years. NFPA 10's hydrostatic test table puts dry chemical extinguishers with stainless steel shells on a 5-year interval, like water, foam and carbon dioxide units. The 12-year interval applies to dry chemical with mild steel, brazed brass or aluminum shells; 6 years is the internal examination interval, not a hydrostatic test.
10. A non-DOT stored-pressure ABC extinguisher is due for its 12-year hydrostatic test. What test pressure should be used?
Answer: The factory test pressure shown on the nameplate. Non-DOT stored-pressure shells are tested at the factory test pressure on the nameplate, which must not exceed twice the service pressure. Five-thirds of service pressure is the DOT rule for carbon dioxide cylinders, and the service pressure alone would not prove the shell.
11. In November 2026, a technician finds a stored-pressure ABC extinguisher made in 2019 with no verification-of-service collar and no record of internal maintenance. What is due?
Answer: The 6-year internal maintenance, which is overdue and should be done now. Stored-pressure extinguishers that need a 12-year hydrostatic test are emptied and given internal maintenance every 6 years, counted from manufacture or the last full internal service. A 2019 unit was due in 2025, so it is overdue; its hydrostatic test falls in 2031.
12. During 6-year maintenance of a halocarbon clean agent extinguisher, how must the agent be removed?
Answer: Transferred with a closed recovery system. Halogenated and halocarbon agents must be removed and held in a closed recovery system so no agent escapes to the atmosphere. Venting or discharging them is not allowed, and removing the valve before the pressure is recovered is also a safety hazard.
13. A shop is recharging a stored-pressure ABC extinguisher. It has an air compressor with a moisture trap and a cylinder of industrial-grade nitrogen. Which expellant gas is correct?
Answer: Nitrogen with a dew point of -60 °F or lower. Dry chemical stored-pressure units are pressurized only with nitrogen of -60 °F dew point or lower, or the gas the manufacturer specifies, because moisture cakes the powder. Compressor air is permitted only for some water-type units, and carbon dioxide is not a substitute expellant.
14. A technician is short of monoammonium phosphate agent and suggests topping up an ABC unit with sodium bicarbonate dry chemical. What is correct?
Answer: It is prohibited; use only the agent on the nameplate. Mixing dry chemicals is prohibited: acidic multipurpose agent and alkaline bicarbonate agents react, releasing gas and moisture that cake the powder and can raise internal pressure. Recharge only with the agent specified on the nameplate, and clean out any unit that has been mixed.
15. During a monthly inspection, the owner's employee finds an ABC extinguisher with the gauge in the green but a cracked discharge hose. What should happen?
Answer: Remove it for maintenance by a certified technician and provide a replacement. Inspection checks for obvious damage, and any deficiency triggers corrective action right away, not at the next annual visit. A cracked hose can fail at discharge, so the unit is sent for maintenance and a spare is put in its place. Taping it does not restore the unit.

Get the full NAFED FE Extinguisher Technician prep

Most popular · cancel anytime

Premium Monthly

$147/month
per exam
About $4.83 a day · less than a single code book, for a certification employers and AHJs ask for by name
  • One NFPA exam of your choice: CFPS, CFI or CFPE
  • 3,000 practice questions + 6 full mock exams per exam
  • 800 flashcards + 60 key notes per exam, by topic, plus mind maps
  • Spaced repetition + mistakes bank
  • Readiness Score & detailed reports
  • Video lessons as they release
  • Content updates during your access
  • 5 bonuses: formulas and values sheet, code values quick reference, study planner and more
  • Pass Guarantee: complete the prep, pass or 100% back

Renews monthly until you cancel. Cancel in two clicks from your account; you keep access until the end of the month you've paid for. No minimum term.

Best value · 3 months free

Premium Yearly

$1,323/year
per exam
Pay for 9 months, get 12. Save $441 against paying monthly.
  • One NFPA exam of your choice: CFPS, CFI or CFPE
  • 3,000 practice questions + 6 full mock exams per exam
  • 800 flashcards + 60 key notes per exam, by topic, plus mind maps
  • Spaced repetition + mistakes bank
  • Readiness Score & detailed reports
  • Video lessons as they release
  • Content updates during your access
  • 5 bonuses: formulas and values sheet, code values quick reference, study planner and more
  • Pass Guarantee: complete the prep, pass or 100% back

Renews once a year until you cancel. We email you before each renewal. Cancel any time from your account; you keep access until the end of the year you've paid for.

Pass Guarantee. Complete the full prep, sit your exam within 60 days, and if you don't pass we refund 100% of your subscription payments. See the requirements
Secure checkout by Stripe Card, Apple Pay, Google Pay Pass Guarantee

NAFED FE Extinguisher Technician exam FAQ

How many questions are on the NAFED FE Extinguisher Technician exam?

100 multiple-choice questions, with a time limit of 2 hours. Format: open book. nafed's references: nfpa 10, standard for portable fire extinguishers and 49 cfr parts 100-185 (nafed publishes a list of the sections to focus on), plus nafed's fire and fire extinguishment (optional). check icc's remote-testing rules for which book formats are allowed.

What is the passing score for NAFED FE Extinguisher Technician?

Scaled score of 75. ICC reports PASS only; failing candidates see the topic areas where they were weak.

How much does the NAFED FE Extinguisher Technician exam cost?

US$320 (NAFED, 2026). Exam purchases are final and valid for 365 days. Fees and reference editions change, so confirm on nfpa.org before you apply.

Which languages is the NAFED FE Extinguisher Technician exam offered in?

English. ICC and NAFED do not list other languages; confirm with ICC.

Where do I take the NAFED FE Extinguisher Technician exam?

ICC, by proctored online testing (PRONTO). Register through the ICC Exam Catalog under the NAFED category.

Is this NAFED FE Extinguisher Technician practice test free?

Yes. The 15-question practice test on this page is free, with an explanation for every answer and no signup. A free account also unlocks the complete study notes for the first topic. The full NAFED FE Extinguisher Technician prep is Premium at $147 a month for this exam.

What's in the premium NAFED FE Extinguisher Technician prep?

3,000 practice questions organized topic by topic (Annual Maintenance: 450; Selection, Placement and Installation: 425; Recordkeeping and Safety: 425; Hydrostatic Testing: 425; 6-Year and Internal Maintenance: 425; Recharging: 425; Inspection: 425), 6 full-length timed mock exams of 100 questions, 800 flashcards and 60 comprehensive key notes split across all 7 topics, plus a mistakes bank and the Readiness Score.

Related practice tests

Exam details are summarized from the official candidate information available in November 2026. NFPA changes formats and fees, so confirm with National Association of Fire Equipment Distributors (NAFED), in a joint program with the International Code Council (ICC), which administers the exam before you book. CFPSExamPrep is not affiliated with NFPA or Prometric.

Start the free test