ICC Fire Alarm Plans Examiner II (CR): free practice test

ICC's advanced certification for plans examiners who review complex systems, including performance-based design, voice evacuation, mass notification, emergency communication, smoke control and advanced detection. Candidates must already hold current CN certification. Documentation and plan reading is 37% of the exam and control panels, wiring and pathways 30%; calculations, notification appliances, initiating devices and control interfaces are 8% to 9% each.

Watch the free 4:55 video lesson: the key ICC Fire Alarm Plans Examiner II concepts →

Premium: 3,000 practice questions, 6 full mock exams, 800 flashcards and 60 comprehensive key notes, topic by topic. See the study path ·

Or open the free ICC Fire Alarm Plans Examiner II study dashboard: flashcards, notes and your Readiness Score, no signup →

About the ICC Fire Alarm Plans Examiner II exam

ICC's advanced certification for plans examiners who review complex systems, including performance-based design, voice evacuation, mass notification, emergency communication, smoke control and advanced detection. Candidates must already hold current CN certification. Documentation and plan reading is 37% of the exam and control panels, wiring and pathways 30%; calculations, notification appliances, initiating devices and control interfaces are 8% to 9% each.

What's on the exam

ICC Fire Alarm Plans Examiner II
Documentation and Plan Reading for Advanced Systems
7 key facts
Advanced Control Panels, Wiring and Pathways
7 key facts
Voice and Advanced System Calculations
6 key facts
Voice, Mass Notification and Visible Appliances
6 key facts
Advanced Initiating Devices
6 key facts
Smoke Control and Advanced Control Interfaces
6 key facts

Each branch is a topic in the official outline. Members see every key fact on the full mind map. Read the free study guide →

How to pass the ICC Fire Alarm Plans Examiner II exam

  • 60 questions in 150 minutes is 2.5 minutes each. Documentation and control equipment are 67% of the exam, so spend most of your study on those two areas.
  • Calculations fall from 20% on CN to 8% on CR. Know the 15-minute voice battery period and speaker level math, but don't prepare as if this were CN.
  • Tab NFPA 72 Chapter 24 (emergency communications), Section 12.4 (pathway survivability), Section 18.4 (intelligibility), Annex D, and IFC Sections 508, 907.5.2.2 and 909.
  • Most questions ask whether a design meets its stated goal. Find the goal in the stem first, then test the proposed equipment or pathway against it.

Save your results and get your Readiness Score

Create a free account after the test: your score by topic, a mistakes bank, the complete study notes for the first topic, flashcards and the Fire Protection Formulas & Values Sheet.

Take the test first

What's in the premium ICC Fire Alarm Plans Examiner II prep

Premium ICC Fire Alarm Plans Examiner II prep is studied one topic at a time. Each step starts with that topic's key notes and flashcard deck, then its own question sets of 25, so you master one topic before you move to the next. When every topic is strong, the 6 full mock exams show you're ready.

3,000practice questions, every answer explained
6full-length mock exams, 60 questions each, timed
800flashcards with spaced repetition, sorted by topic
60comprehensive key notes across 6 topics

Your step-by-step study path

  1. 1
    Documentation and Plan Reading for Advanced Systems10 key notes, 135 flashcards, then 500 practice questions in 20 sets of 25
    Notes free with an account
  2. 2
    Advanced Control Panels, Wiring and Pathways10 key notes, 135 flashcards, then 500 practice questions in 20 sets of 25
    Premium
  3. 3
    Voice and Advanced System Calculations10 key notes, 135 flashcards, then 500 practice questions in 20 sets of 25
    Premium
  4. 4
    Voice, Mass Notification and Visible Appliances10 key notes, 135 flashcards, then 500 practice questions in 20 sets of 25
    Premium
  5. 5
    Advanced Initiating Devices10 key notes, 130 flashcards, then 500 practice questions in 20 sets of 25
    Premium
  6. 6
    Smoke Control and Advanced Control Interfaces10 key notes, 130 flashcards, then 500 practice questions in 20 sets of 25
    Premium
  7. Final step: 6 full mock exams60 questions each, timed like test day. Pass them, then book your exam.
    Premium
Free with an account

Read the complete ICC Fire Alarm Plans Examiner II study notes for “Documentation and Plan Reading for Advanced Systems”

Our first full set of comprehensive notes, about 15 minutes of reading: Risk assessment · Design goals and performance-based design · Design calculations · Listing information and compatibility · Documentation and acoustically distinguishable spaces, a worked exam example, the traps examiners use and a one-minute recap. Create a free account to read it and see how premium notes work before you decide.

Open the free dashboard

Study tools included

3,000 practice questions

3,000 exam-style questions per exam, organized topic by topic in sets of 25. Every answer explained, with the rule it comes from.

6 full mock exams

6 full-length timed mock exams per exam, with real question counts and time limits, so test day feels like practice day.

Exam Readiness Score

One 0 to 100 number that tells you when you're ready to book. Reach 80 and you're covered by our Pass Guarantee.

800 flashcards + spaced repetition

800 flashcards per exam, in a deck for each topic, that come back right before you'd forget them. Five minutes a day keeps every number fresh.

60 comprehensive key notes

60 key notes per exam, split across its topics and each explained in full: the concepts, worked exam examples, the traps examiners use and a quick recap. Your first set is free with an account.

Mind maps

See the whole exam on one screen: every topic and the facts under it.

Sample questions with answers

These are the questions in the free test above, with answers. Try the test first. You'll learn more by getting some wrong.

1. An in-building mass notification design for a corporate campus programs security lockdown messages to override the fire alarm evacuation message. The submittal contains no risk analysis. What should plan review require?
Answer: A documented risk analysis that supports the message priority. NFPA 72 Chapters 10 and 24 allow mass notification messages to take priority over fire alarm signals only where a risk analysis supports it. An automatic ban is wrong, because some threats are more urgent than a fire signal. A listing or owner letter doesn't replace the facility-specific analysis.
2. A submittal proposes performance-based smoke detection in a 70-ft atrium in place of prescriptive spacing. It contains only device layouts and data sheets. What is the main deficiency?
Answer: No design goals, performance criteria, fire scenarios or analysis. NFPA 72 Chapter 7 requires performance-based designs to document the goals, performance criteria, design fire scenarios, assumptions and the analysis showing the criteria are met, subject to approval by the authority. Layouts show what is proposed but not why it works. Without that record, the examiner has nothing to evaluate.
3. In a voice evacuation design, a mechanical room with 95 dBA ambient noise is marked as an acoustically distinguishable space where voice intelligibility isn't required. Tone signaling and strobes are provided there. How should the examiner treat this?
Answer: Accept it in principle: not every such space needs intelligible voice. NFPA 72 Section 18.4 has the designer identify acoustically distinguishable spaces and state which need intelligible voice; not all do. High-noise rooms may rely on tone and visible signaling, provided occupants are still notified. The examiner confirms the decision is documented, rather than demanding speech everywhere.
4. A mechanical smoke control system for an atrium is run through a building automation controller with only a general HVAC control listing. What does IFC Section 909 require of the control equipment?
Answer: A control unit complying with UL 864 and listed for smoke control. IFC 909.12 requires smoke control systems to use a control unit complying with UL 864 and listed as smoke control equipment, the UUKL product category. A building automation system can be used only if it carries that listing. UL 268 applies to smoke detectors, not controllers.
5. A high-rise voice system uses partial evacuation. Circuits between the fire command center and the floor amplifiers are Class A in metal conduit, and the building is fully sprinklered. What should the examiner conclude under NFPA 72?
Answer: Not enough: partial evacuation needs Level 2 or Level 3 survivability. NFPA 72 Chapter 24 requires pathway survivability Level 2 or Level 3 for systems using relocation or partial evacuation, meaning 2-hour rated protection. Metal raceway in a sprinklered building is only Level 1. Class describes circuit behavior on faults, while survivability describes how long a pathway lasts in a fire, so one doesn't satisfy the other.
6. A high-rise has a total building area of 1,900,000 sq ft. Under IFC Section 508, what minimum floor area and minimum room dimension must its fire command center have?
Answer: 285 sq ft, 11.8 ft minimum. Area is the greater of 0.015% of building area or 200 sq ft: 1,900,000 x 0.00015 = 285 sq ft. Minimum dimension is the greater of 0.7 times the square root of the room area or 10 ft: 0.7 x 16.88 = 11.8 ft. Stopping at 10 ft misses the area-based dimension, and 16.9 ft forgets the 0.7 factor.
7. A voice system has control locations at the fire command center and a security desk. The sequence of operation lets staff at both locations page the same speakers at the same time. What should the examiner require under NFPA 72 Chapter 24?
Answer: Only one location in control at a time, with a visible indication. Where there are multiple control locations, only one may be in control at any given time, and the location in control must be visibly indicated. Multiple locations are permitted, so removing one isn't necessary. Circuit class has nothing to do with competing live messages.
8. Drawings call for 2-hour circuit integrity cable to be pulled through PVC conduit and supported with nylon ties. The cable's fire-resistive listing covers only steel conduit with steel supports. What should the examiner decide?
Answer: Reject it: the cable must be installed as its listed system requires. Under NEC Article 728, a fire-resistive cable system earns its rating only as a tested assembly, including its raceway, supports and fittings. PVC and nylon would fail early in a fire and take the cable down. Check the listing's installation details, not just the cable type.
9. A voice evacuation panel draws 2.1 A in standby and 14.5 A at maximum connected load in alarm. Using 24 hours of standby, the required voice alarm period and the 20% safety margin in NFPA 72, what minimum battery capacity is needed?
Answer: 64.8 Ah. Standby is 2.1 x 24 = 50.4 Ah. Voice systems need 15 minutes at maximum connected load: 14.5 x 0.25 = 3.63 Ah, for 54.03 Ah total. With the 20% margin, 54.03 x 1.2 = 64.8 Ah. Using 5 minutes of alarm gives 61.9 Ah, which is the non-voice period.
10. A speaker is rated 86 dBA at 10 ft on its 1-W tap. The design needs 75 dBA at 40 ft in a space treated as a free field. Taps of 1, 2, 4 and 8 W are available. What is the lowest tap that meets the design?
Answer: 2 W. Sound falls 6 dB per doubling of distance, and 10 ft to 40 ft is two doublings, so 86 - 12 = 74 dBA at 1 W. Each doubling of power adds 3 dB, so 2 W gives 77 dBA and meets 75 dBA. Using 3 dB per doubling of distance wrongly suggests that 1 W is enough.
11. A combined fire and mass notification system uses one strobe in each corridor for both fire and non-fire events. The submitted strobes have FIRE printed on the housing. What should the examiner require under NFPA 72 Chapter 24?
Answer: Change them: appliances used for mass notification can't show FIRE. Visible appliances used for mass notification must not carry the word FIRE or a fire symbol visible to the public, since occupants would misread a non-fire alert. A shared appliance can simply be unmarked or marked ALERT. Separate strobes aren't required, and lens color doesn't fix the misleading label.
12. Within one acoustically distinguishable space, test results show an average STI of 0.52, with 78% of measurement locations at 0.45 or higher. Using the guideline in NFPA 72 Annex D, how should these results be judged?
Answer: Does not meet it: at least 90% of locations should reach 0.45. Annex D's guideline looks for an average of at least 0.50 STI with at least 90% of locations at 0.45 or higher, so both tests must pass. Here the average passes but the location share doesn't. The value 0.70 is the equivalent average on the CIS scale, not an STI target.
13. An air-sampling smoke detection calculation shows a transport time of 135 seconds from the farthest sampling port to the detector. What should the plans examiner decide under NFPA 72?
Answer: Reject it: the maximum transport time is 120 seconds. NFPA 72 Chapter 17 limits air-sampling transport from the farthest port to the detector to 120 seconds. The designer can shorten pipe runs, split the network or add a detector. Each sampling port is also treated as a spot-type detector when checking spacing.
14. A flame detector is listed to detect a 1 sq ft fire at 60 ft on its axis. Assuming fire radiant output is proportional to fire area, and ignoring atmospheric absorption, what fire area produces the same detector response at 30 ft?
Answer: 0.25 sq ft. Radiant energy at the detector follows the inverse square law, so halving the distance increases received energy four times. A fire of one quarter the area, 0.25 sq ft, gives the same response. Linear reasoning gives 0.5 sq ft and misses the squared term, a key point in the engineering evaluation Chapter 17 requires.
15. During a smoke control event, a firefighter uses the firefighter's smoke-control panel to start a supply fan, while a duct smoke detector's automatic shutdown signal is active on that same fan. Under IFC 909.16.3, what should happen?
Answer: The panel command prevails, and its last control action stands. IFC 909.16.3 gives the firefighter's smoke-control panel the highest priority of any control point. Automatic protective devices such as duct smoke detectors and freezestats must be capable of being overridden by it, and the last control action prevails. The sequence of operation should show this explicitly.

Get the full ICC Fire Alarm Plans Examiner II prep

Most popular · cancel anytime

Premium Monthly

$147/month
per exam
About $4.83 a day · less than a single code book, for a certification employers and AHJs ask for by name
  • One NFPA exam of your choice: CFPS, CFI or CFPE
  • 3,000 practice questions + 6 full mock exams per exam
  • 800 flashcards + 60 key notes per exam, by topic, plus mind maps
  • Spaced repetition + mistakes bank
  • Readiness Score & detailed reports
  • Video lessons as they release
  • Content updates during your access
  • 5 bonuses: formulas and values sheet, code values quick reference, study planner and more
  • Pass Guarantee: complete the prep, pass or 100% back

Renews monthly until you cancel. Cancel in two clicks from your account; you keep access until the end of the month you've paid for. No minimum term.

Best value · 3 months free

Premium Yearly

$1,323/year
per exam
Pay for 9 months, get 12. Save $441 against paying monthly.
  • One NFPA exam of your choice: CFPS, CFI or CFPE
  • 3,000 practice questions + 6 full mock exams per exam
  • 800 flashcards + 60 key notes per exam, by topic, plus mind maps
  • Spaced repetition + mistakes bank
  • Readiness Score & detailed reports
  • Video lessons as they release
  • Content updates during your access
  • 5 bonuses: formulas and values sheet, code values quick reference, study planner and more
  • Pass Guarantee: complete the prep, pass or 100% back

Renews once a year until you cancel. We email you before each renewal. Cancel any time from your account; you keep access until the end of the year you've paid for.

Pass Guarantee. Complete the full prep, sit your exam within 60 days, and if you don't pass we refund 100% of your subscription payments. See the requirements
Secure checkout by Stripe Card, Apple Pay, Google Pay Pass Guarantee

ICC Fire Alarm Plans Examiner II exam FAQ

How many questions are on the ICC Fire Alarm Plans Examiner II exam?

60 multiple-choice questions, with a time limit of 2.5 hours. Format: open book. icc's catalog lists the ibc and ifc (both also provided as free digital references during the exam), nfpa 72, nfpa 70, fire alarm signaling systems, and either the nfpa pocket guide to fire alarm and signaling system installation or ugly's electrical reference (any edition). bound, copyrighted books are allowed; study guides and practice questions are not. a newer-edition version is also offered: confirm its reference list in the icc catalog before buying books.

What is the passing score for ICC Fire Alarm Plans Examiner II?

Scaled score of 75 (ICC national certification standard); ICC does not publish the raw percentage, which varies by exam form.

How much does the ICC Fire Alarm Plans Examiner II exam cost?

US$320 (ICC catalog price for PRONTO delivery; ICC members pay a discounted price). Fees and reference editions change, so confirm on nfpa.org before you apply.

Which languages is the ICC Fire Alarm Plans Examiner II exam offered in?

English. ICC's catalog does not list other languages; confirm with ICC.

Where do I take the ICC Fire Alarm Plans Examiner II exam?

ICC PRONTO: in person at a test center or online with remote proctoring.

Is this ICC Fire Alarm Plans Examiner II practice test free?

Yes. The 15-question practice test on this page is free, with an explanation for every answer and no signup. A free account also unlocks the complete study notes for the first topic. The full ICC Fire Alarm Plans Examiner II prep is Premium at $147 a month for this exam.

What's in the premium ICC Fire Alarm Plans Examiner II prep?

3,000 practice questions organized topic by topic (Documentation and Plan Reading for Advanced Systems: 500; Advanced Control Panels, Wiring and Pathways: 500; Voice and Advanced System Calculations: 500; Voice, Mass Notification and Visible Appliances: 500; Advanced Initiating Devices: 500; Smoke Control and Advanced Control Interfaces: 500), 6 full-length timed mock exams of 60 questions, 800 flashcards and 60 comprehensive key notes split across all 6 topics, plus a mistakes bank and the Readiness Score.