Try the full study dashboard free, no signup: practice, flashcards and your Exam Readiness Score. Open it →
Home / Practice tests / NICET IB-PSC Design
NICET · Last updated November 2026

NICET In-Building Public Safety Communications Design: free practice test

The single-level design track of NICET's In-Building Public Safety Communications program, developed with the Safer Buildings Coalition. Its 110 questions cover project scope (15-25%), RF signal strength and quality (25-35%) and system design (45-55%). Questions moved from NFPA 1221 to NFPA 1225 on December 2, 2024. This prep covers the written exam only; the work history, performance measures and recommendation are separate requirements.

Watch the free 4:29 video lesson: the key NICET IB-PSC Design concepts →

Premium: 3,000 practice questions, 6 full mock exams, 800 flashcards and 60 comprehensive key notes, topic by topic. See the study path ·

Or open the free NICET IB-PSC Design study dashboard: flashcards, notes and your Readiness Score, no signup →

About the NICET IB-PSC Design exam

The single-level design track of NICET's In-Building Public Safety Communications program, developed with the Safer Buildings Coalition. Its 110 questions cover project scope (15-25%), RF signal strength and quality (25-35%) and system design (45-55%). Questions moved from NFPA 1221 to NFPA 1225 on December 2, 2024. This prep covers the written exam only; the work history, performance measures and recommendation are separate requirements.

What's on the exam

NICET IB-PSC Design
Project Specifications and Code Criteria
7 key facts
Project Drawings and Site Survey Reports
7 key facts
Potential RF Interference
7 key facts
Field Observations and RF Results
7 key facts
Design Application Parameters
7 key facts
Equipment Selection and Headend Planning
7 key facts
System Layout
7 key facts
Bill of Materials and Submittal Packages
7 key facts

Each branch is a topic in the official outline. Members see every key fact on the full mind map. Read the free study guide →

How to pass the NICET IB-PSC Design exam

  • 110 questions in 150 minutes is about 82 seconds each. Practice dB arithmetic until link budgets take well under a minute, and save lookups for code clauses.
  • System design is about half the exam. Isolation, per-channel power, splitter loss and path loss should be automatic.
  • Bring the listed editions. NICET bases questions on the editions of NFPA 1225 and IFC that it lists, and comments based on other editions are not reviewed until the next maintenance cycle.
  • Tab NFPA 1225 Chapter 18 by coverage, signal quality, donor isolation, survivability, power and monitoring, and tab 47 CFR 90.219 for booster classes and limits.

Save your results and get your Readiness Score

Create a free account after the test: your score by topic, a mistakes bank, the complete study notes for the first topic, flashcards and the Fire Protection Formulas & Values Sheet.

Take the test first

What's in the premium NICET IB-PSC Design prep

Premium NICET IB-PSC Design prep is studied one topic at a time. Each step starts with that topic's key notes and flashcard deck, then its own question sets of 25, so you master one topic before you move to the next. When every topic is strong, the 6 full mock exams show you're ready.

3,000practice questions, every answer explained
6full-length mock exams, 110 questions each, timed
800flashcards with spaced repetition, sorted by topic
60comprehensive key notes across 8 topics

Your step-by-step study path

  1. 1
    Project Specifications and Code Criteria8 key notes, 100 flashcards, then 375 practice questions in 15 sets of 25
    Notes free with an account
  2. 2
    Project Drawings and Site Survey Reports8 key notes, 100 flashcards, then 375 practice questions in 15 sets of 25
    Premium
  3. 3
    Potential RF Interference8 key notes, 100 flashcards, then 375 practice questions in 15 sets of 25
    Premium
  4. 4
    Field Observations and RF Results8 key notes, 100 flashcards, then 375 practice questions in 15 sets of 25
    Premium
  5. 5
    Design Application Parameters7 key notes, 100 flashcards, then 375 practice questions in 15 sets of 25
    Premium
  6. 6
    Equipment Selection and Headend Planning7 key notes, 100 flashcards, then 375 practice questions in 15 sets of 25
    Premium
  7. 7
    System Layout7 key notes, 100 flashcards, then 375 practice questions in 15 sets of 25
    Premium
  8. 8
    Bill of Materials and Submittal Packages7 key notes, 100 flashcards, then 375 practice questions in 15 sets of 25
    Premium
  9. Final step: 6 full mock exams110 questions each, timed like test day. Pass them, then book your exam.
    Premium
Free with an account

Read the complete NICET IB-PSC Design study notes for “Project Specifications and Code Criteria”

Our first full set of comprehensive notes, about 14 minutes of reading: Which documents control · Coverage and quality targets · Approvals and FCC consent · Limits to carry into the design, a worked exam example, the traps examiners use and a one-minute recap. Create a free account to read it and see how premium notes work before you decide.

Open the free dashboard

Study tools included

3,000 practice questions

3,000 exam-style questions per exam, organized topic by topic in sets of 25. Every answer explained, with the rule it comes from.

6 full mock exams

6 full-length timed mock exams per exam, with real question counts and time limits, so test day feels like practice day.

Exam Readiness Score

One 0 to 100 number that tells you when you're ready to book. Reach 80 and you're covered by our Pass Guarantee.

800 flashcards + spaced repetition

800 flashcards per exam, in a deck for each topic, that come back right before you'd forget them. Five minutes a day keeps every number fresh.

60 comprehensive key notes

60 key notes per exam, split across its topics and each explained in full: the concepts, worked exam examples, the traps examiners use and a quick recap. Your first set is free with an account.

Mind maps

See the whole exam on one screen: every topic and the facts under it.

Sample questions with answers

These are the questions in the free test above, with answers. Try the test first. You'll learn more by getting some wrong.

1. A project specification calls for 90% radio coverage on every floor, and the adopted standard is NFPA 1225. Your model shows DAQ 3.0 or better on 96% of general floor area and 97.5% of exit stair floor area. What should you do?
Answer: Add coverage in the stairs, which need 99%; general areas meet 95%. NFPA 1225 Chapter 18 requires 95% floor-area coverage in general building areas and 99% in critical areas such as exit stairs. A looser project specification does not lower the adopted standard, so 96% passes and 97.5% does not. Design to the stricter of the specification and the adopted code, and raise the conflict by RFI.
2. The specification for an 800 MHz ERCES calls for a booster with a single 18 MHz passband. The building owner, not the radio licensee, will operate it. What does 47 CFR 90.219 require?
Answer: The intended licensee's express consent, plus FCC registration. A passband over 75 kHz makes this a Class B booster, and Class B installations must be registered in the FCC signal booster database. A non-licensee operator needs the express consent of the licensee whose frequencies it intends to amplify, kept in a recordable format. Unintended third-party licensees need not consent, but operation stays on a non-interference basis.
3. Sheet G-001 lists a 14-story high-rise, Type IB construction with a 2-hour primary structural frame, and NFPA 13 sprinklers throughout. Under NFPA 1225, how must the backbone cable be protected?
Answer: 2-hour listed cable or a 2-hour enclosure or protected area. The sprinkler exemption does not reach high-rise buildings, so the backbone must be protected. The rating follows the primary structural frame: 2 hours where the frame is rated 2 hours or more or is heavy timber, 1 hour where it is rated less. Rated cable and a rated enclosure or protected area are both acceptable methods.
4. Two strong downlink carriers at 851.2125 MHz and 852.0625 MHz pass through a booster. At what frequency does the third-order intermodulation product above the pair fall?
Answer: 852.9125 MHz. Third-order products are at 2f1 - f2 and 2f2 - f1. The upper one is 2(852.0625) - 851.2125 = 852.9125 MHz; the lower one is 850.3625 MHz. 853.7625 MHz is the fifth-order product 3f2 - 2f1. Check these products against the licensed channel list before you combine carriers.
5. A channelized booster has 55 dB of uplink gain and a 6 dB noise figure. Thermal noise is -174 dBm/Hz. What uplink noise power appears at its output in a 12.5 kHz bandwidth?
Answer: -72 dBm. Noise in 12.5 kHz is -174 + 10 log(12,500) = -133 dBm. Adding the 6 dB noise figure gives -127 dBm and the 55 dB of gain gives -72 dBm. Omitting the noise figure gives -78 dBm. NFPA 1225 does not allow booster uplink noise to raise the noise floor at the public safety site.
6. On a P25 system, one grid center reads -91 dBm, with interference plus noise at -106 dBm and a BER of 3.0%. The AHJ uses the NFPA 1225 annex criteria of SINR at least 18 dB and BER at most 2.5%. How should the point be recorded?
Answer: Fail, because SINR is 15 dB and BER is over the limit. SINR is -91 - (-106) = 15 dB, below 18 dB, and the 3.0% BER exceeds 2.5%. Signal strength alone does not prove usable audio: a strong signal in a noisy environment can still fall short of DAQ 3.0. Record quality as well as level on digital systems.
7. A roof survey reads Site A at -62 dBm and Site B at -71 dBm. The licensee's technical criteria name Site B as the donor for this building. What should the design do?
Answer: Aim a directional donor antenna at Site B, confirming levels with the licensee. The frequency license holder controls which site the system may use, and NFPA 1225 requires its approval of the design. A directional antenna also rejects the stronger undesired site. An omni donor would admit both sites, which can cause time-delay interference and capture problems.
8. An acceptance test under IFC (2018) divides a floor into 20 approximately equal test areas, and exactly two areas fail. What does the code allow next?
Answer: Re-divide the floor into 40 areas, with up to two nonadjacent failures. IFC (2018) Section 510 fails a floor on more than one failed area out of 20, but two failures allow a 40-area retest with not more than two nonadjacent failures. The test point at the approximate center represents the whole cell, so added spots inside a cell are not allowed. Earlier IFC editions used a 90% criterion, which is the trap here.
9. A donor site has an EIRP of +52 dBm and is 5 km away at 851 MHz. Assuming free-space loss, a donor antenna gain of 11 dBi and 2 dB of donor cable loss, what level reaches the booster input?
Answer: -44 dBm. Free-space loss is 32.45 + 20 log(851) + 20 log(5) = 105 dB. The level is 52 - 105 + 11 - 2 = -44 dBm. Leaving out antenna gain gives -55 dBm, and subtracting it gives -66 dBm. Real paths add clutter loss, so confirm the model with a roof measurement.
10. The AHJ's technical criteria set a maximum propagation delay of 14 microseconds. Headend and remote electronics add 9 microseconds, and fiber adds 5 microseconds per km. What is the longest allowable fiber run?
Answer: 1.0 km. The delay left for fiber is 14 - 9 = 5 microseconds, and 5 / 5 = 1.0 km. Dividing 9 or 14 by 5 forgets to take electronics out of the budget. Delay matters most on simulcast systems, where it causes time-delay interference, so enter the AHJ limit before fixing the headend location.
11. A booster is rated at +33 dBm composite downlink output and will carry 16 equal-power channels. Ignoring any manufacturer derating, what is the maximum output per channel?
Answer: 21 dBm. Composite power divides by channel count: 33 - 10 log(16) = 33 - 12 = 21 dBm. Using 20 log gives 9 dBm, and dividing dBm values directly gives about 2 dBm, which has no physical meaning. Check the manufacturer's table too, since intermodulation limits can derate output further.
12. Measured isolation between the donor antenna and the nearest inside antenna is 88 dB, and the design calls for 75 dB of booster gain. Under NFPA 1225, what is the maximum system gain?
Answer: 68 dB. Isolation must be at least 20 dB above system gain, so maximum gain is 88 - 20 = 68 dB. The planned 75 dB would leave only 13 dB of margin and risk oscillation. Reduce gain, or increase isolation by moving the donor antenna or improving its front-to-back ratio.
13. A channel leaves the booster at +24 dBm, then passes 200 ft of coax at 2.0 dB per 100 ft, a 4-way splitter (6.5 dB), a 2-way splitter (3.5 dB) and a 2 dBi antenna. For a -85 dBm design level and a 0 dBi portable, what is the maximum allowable path loss?
Answer: 97 dB. EIRP is 24 - 4 - 6.5 - 3.5 + 2 = 12 dBm. Maximum path loss is 12 - (-85) = 97 dB. Using -95 dBm gives 107 dB, which leaves no margin for fading, body loss or model error. Run the same budget on the uplink, because the weaker direction sets antenna spacing.
14. On a long hotel floor served by one high-power antenna, a portable near the antenna drives the uplink limiter and a portable at the far end loses its uplink. What is the best design change?
Answer: Use more antennas at lower power to even out the path loss. This is the near-far problem: a strong nearby portable captures the booster's uplink gain control and suppresses a distant one. Greater antenna density evens out path losses, and NFPA 1225 expects enough distribution antennas to cope with reduced-gain conditions. Raising downlink power does nothing for the uplink.
15. A reviewer rejects a submittal because nothing shows that the 20 dB rule is met. The package already has antenna locations, heat maps, battery calculations and cut sheets. What must be added?
Answer: Donor-to-DAS antenna isolation calculations. The 20 dB rule compares donor-to-inside-antenna isolation with system gain, so the reviewer needs the isolation calculations. The NFPA 1225 annex lists these among the design documents for approval, along with link budgets, signal source levels and test grids. Grounding, power and survivability details are also needed but prove other requirements.

Get the full NICET IB-PSC Design prep

Most popular · cancel anytime

Premium Monthly

$147/month
per exam
About $4.83 a day · less than a single code book, for a certification employers and AHJs ask for by name
  • One NFPA exam of your choice: CFPS, CFI or CFPE
  • 3,000 practice questions + 6 full mock exams per exam
  • 800 flashcards + 60 key notes per exam, by topic, plus mind maps
  • Spaced repetition + mistakes bank
  • Readiness Score & detailed reports
  • Video lessons as they release
  • Content updates during your access
  • 5 bonuses: formulas and values sheet, code values quick reference, study planner and more
  • Pass Guarantee: complete the prep, pass or 100% back

Renews monthly until you cancel. Cancel in two clicks from your account; you keep access until the end of the month you've paid for. No minimum term.

Best value · 3 months free

Premium Yearly

$1,323/year
per exam
Pay for 9 months, get 12. Save $441 against paying monthly.
  • One NFPA exam of your choice: CFPS, CFI or CFPE
  • 3,000 practice questions + 6 full mock exams per exam
  • 800 flashcards + 60 key notes per exam, by topic, plus mind maps
  • Spaced repetition + mistakes bank
  • Readiness Score & detailed reports
  • Video lessons as they release
  • Content updates during your access
  • 5 bonuses: formulas and values sheet, code values quick reference, study planner and more
  • Pass Guarantee: complete the prep, pass or 100% back

Renews once a year until you cancel. We email you before each renewal. Cancel any time from your account; you keep access until the end of the year you've paid for.

Pass Guarantee. Complete the full prep, sit your exam within 60 days, and if you don't pass we refund 100% of your subscription payments. See the requirements
Secure checkout by Stripe Card, Apple Pay, Google Pay Pass Guarantee

NICET IB-PSC Design exam FAQ

How many questions are on the NICET IB-PSC Design exam?

110 questions, with a time limit of 150 minutes, plus a 10-minute tutorial before the exam clock starts. Format: open book. you may bring bound or binder-secured nfpa 1225, 47 cfr part 90, the complete erces handbook, the international fire code and indoor radio planning, with permanently attached tabs and no handwritten notes. nfpa handbooks are not accepted. built-in calculators only. some items may ask for more than one answer or a click on a picture; this prep uses 4-option single-best-answer questions.

What is the passing score for NICET IB-PSC Design?

Not published by NICET. Pass or fail is shown at the end of the session; failing candidates get a scaled score with percent correct by domain. Retakes after 30 days, up to 3 attempts in any 12 months.

How much does the NICET IB-PSC Design exam cost?

US$380 application and exam fee (effective 1 Aug 2026). Rescheduling for a new testing window or within 24 hours costs half the original fee. Fees and reference editions change, so confirm on nfpa.org before you apply.

Which languages is the NICET IB-PSC Design exam offered in?

English only.

Where do I take the NICET IB-PSC Design exam?

Pearson VUE: computer-based at Pearson VUE test centers, booked within a six-month testing window.

Is this NICET IB-PSC Design practice test free?

Yes. The 15-question practice test on this page is free, with an explanation for every answer and no signup. A free account also unlocks the complete study notes for the first topic. The full NICET IB-PSC Design prep is Premium at $147 a month for this exam.

What's in the premium NICET IB-PSC Design prep?

3,000 practice questions organized topic by topic (Project Specifications and Code Criteria: 375; Project Drawings and Site Survey Reports: 375; Potential RF Interference: 375; Field Observations and RF Results: 375; Design Application Parameters: 375; Equipment Selection and Headend Planning: 375; System Layout: 375; Bill of Materials and Submittal Packages: 375), 6 full-length timed mock exams of 110 questions, 800 flashcards and 60 comprehensive key notes split across all 8 topics, plus a mistakes bank and the Readiness Score.

Related practice tests

Exam details are summarized from the official candidate information available in November 2026. NFPA changes formats and fees, so confirm with National Institute for Certification in Engineering Technologies (NICET) before you book. CFPSExamPrep is not affiliated with NFPA or Prometric.

Start the free test