Certified Sprinkler ITM Specialist for Facility Managers (CSITMS): free practice test

NFPA's credential for facility managers who keep sprinkler and other water-based fire protection systems compliant with NFPA 25. The exam is based on the edition named by the exam body, which may not be the current one. Domain weights are General Requirements 18%, Inspection 24%, Testing 22%, Maintenance 22%, and Obstruction Investigation and Impairments 14%.

Watch the free 4:06 video lesson: the key CSITMS concepts →

Premium: 3,000 practice questions, 6 full mock exams, 800 flashcards and 60 comprehensive key notes, topic by topic. See the study path ·

Or open the free CSITMS study dashboard: flashcards, notes and your Readiness Score, no signup →

About the CSITMS exam

NFPA's credential for facility managers who keep sprinkler and other water-based fire protection systems compliant with NFPA 25. The exam is based on the edition named by the exam body, which may not be the current one. Domain weights are General Requirements 18%, Inspection 24%, Testing 22%, Maintenance 22%, and Obstruction Investigation and Impairments 14%.

What's on the exam

CSITMS
General Requirements
8 key facts
Inspection
7 key facts
Testing
8 key facts
Maintenance
7 key facts
Internal Piping Condition and Obstruction Investigation
6 key facts
Impairments
7 key facts

Each branch is a topic in the official outline. Members see every key fact on the full mind map. Read the free study guide →

How to pass the CSITMS exam

  • The exam tests the edition of NFPA 25 named by the exam body. Several intervals changed in later editions (dry sprinklers, wet system gauges, some valve inspections), so study from that edition, not a newer one.
  • Three hours for 100 questions is 1 minute 48 seconds each. Tab the summary tables at the start of Chapters 5 to 9 and 13 so frequency lookups take seconds.
  • Chapter 13 (valves, trim, FDCs, backflow and pressure-regulating devices) shows up in every domain of the blueprint. Learn its layout well.
  • Chapters 14 and 15 carry 14% between them and are short. Read both end to end, especially who must be notified and what happens before and after an impairment.

Save your results and get your Readiness Score

Create a free account after the test: your score by topic, a mistakes bank, the complete study notes for the first topic, flashcards and the Fire Protection Formulas & Values Sheet.

Take the test first

What's in the premium CSITMS prep

Premium CSITMS prep is studied one topic at a time. Each step starts with that topic's key notes and flashcard deck, then its own question sets of 25, so you master one topic before you move to the next. When every topic is strong, the 6 full mock exams show you're ready.

3,000practice questions, every answer explained
6full-length mock exams, 100 questions each, timed
800flashcards with spaced repetition, sorted by topic
60comprehensive key notes across 6 topics

Your step-by-step study path

  1. 1
    General Requirements10 key notes, 135 flashcards, then 500 practice questions in 20 sets of 25
    Notes free with an account
  2. 2
    Inspection10 key notes, 135 flashcards, then 500 practice questions in 20 sets of 25
    Premium
  3. 3
    Testing10 key notes, 135 flashcards, then 500 practice questions in 20 sets of 25
    Premium
  4. 4
    Maintenance10 key notes, 135 flashcards, then 500 practice questions in 20 sets of 25
    Premium
  5. 5
    Internal Piping Condition and Obstruction Investigation10 key notes, 130 flashcards, then 500 practice questions in 20 sets of 25
    Premium
  6. 6
    Impairments10 key notes, 130 flashcards, then 500 practice questions in 20 sets of 25
    Premium
  7. Final step: 6 full mock exams100 questions each, timed like test day. Pass them, then book your exam.
    Premium
Free with an account

Read the complete CSITMS study notes for “General Requirements”

Our first full set of comprehensive notes, about 14 minutes of reading: Owner responsibilities (Chapter 4) · Key definitions (Chapter 3) · Records · Control valves and gauges (Chapter 13), a worked exam example, the traps examiners use and a one-minute recap. Create a free account to read it and see how premium notes work before you decide.

Open the free dashboard

Study tools included

3,000 practice questions

3,000 exam-style questions per exam, organized topic by topic in sets of 25. Every answer explained, with the rule it comes from.

6 full mock exams

6 full-length timed mock exams per exam, with real question counts and time limits, so test day feels like practice day.

Exam Readiness Score

One 0 to 100 number that tells you when you're ready to book. Reach 80 and you're covered by our Pass Guarantee.

800 flashcards + spaced repetition

800 flashcards per exam, in a deck for each topic, that come back right before you'd forget them. Five minutes a day keeps every number fresh.

60 comprehensive key notes

60 key notes per exam, split across its topics and each explained in full: the concepts, worked exam examples, the traps examiners use and a quick recap. Your first set is free with an account.

Mind maps

See the whole exam on one screen: every topic and the facts under it.

Sample questions with answers

These are the questions in the free test above, with answers. Try the test first. You'll learn more by getting some wrong.

1. An owner leases an entire office building to a single tenant. The lease states that the tenant will arrange all sprinkler inspection, testing and maintenance. Under NFPA 25, who holds that authority?
Answer: The tenant, because a specific lease provision may pass the authority to the occupant. NFPA 25 makes the owner or designated representative responsible, but where the owner is not the occupant it allows the authority to be passed to the occupant, a management firm or a managing individual through specific provisions in a lease, written use agreement or management contract. The AHJ enforces; it does not take over ITM duties.
2. A warehouse protected for storage of boxed metal parts will start storing cartoned expanded plastic goods next month. What does NFPA 25 require before the change?
Answer: An evaluation of whether the system can protect the new commodity. Chapter 4 says the owner or occupant must not change the occupancy, use, process or stored materials without evaluating the fire protection system's capability to protect them. Plastics are a much higher hazard than metal parts, so the design may be inadequate. A main drain test checks supply, not design adequacy.
3. A facility secures every sprinkler control valve with a padlock and chain. The valves are not electrically supervised. How often must they be inspected under NFPA 25?
Answer: Monthly. Sealed valves need weekly inspection, while valves secured with locks or electrically supervised may be inspected monthly. Annual is the interval for operating each valve through its full range, which is a test, not the position inspection.
4. During the annual floor-level inspection, a facility manager finds that painters coated several corridor sprinklers with latex paint. What does NFPA 25 require?
Answer: Replace the painted sprinklers with ones of like characteristics. Sprinklers painted other than by the manufacturer must be replaced, because paint can delay operation or glue the cap in place. Solvent can damage the operating element, so cleaning is not the fix. Replacements must match the original type, orifice, temperature rating and response.
5. In a storage room protected by standard spray upright sprinklers, the inspector measures stacked boxes 12 in. below the sprinkler deflectors. What is the correct finding?
Answer: Deficient: keep at least 18 in. of clearance below the deflectors. NFPA 25 requires the clearance from the installation standard to be kept below all sprinklers, and NFPA 13 sets 18 in. for standard spray sprinklers. Stock closer than that blocks the spray pattern and must be moved. The 36 in. figure is the ESFR clearance.
6. On the weekly fire pump inspection, a pump room containing a diesel engine-driven pump with no engine heater is at 55°F. What is the finding under NFPA 25?
Answer: Deficient: this room must be kept at no less than 70°F. The weekly pump house check requires at least 40°F, raised to 70°F for rooms with diesel pumps that do not have engine heaters, so a cold engine will start reliably. The 40°F figure is the tempting answer because it applies to electric pumps and heated diesel engines.
7. During the quarterly fire department connection inspection, two inlet caps are missing. Apart from replacing the caps, what else must be done?
Answer: Inspect the inlets for obstructions and check the clapper works over its range. Missing plugs or caps let debris and objects get into the inlet, so NFPA 25 requires the interior to be inspected for obstructions and the clapper to be verified operational over its full range. A hydrostatic test checks piping strength and would not find debris jammed in the inlet.
8. A 0 to 300 psi riser gauge is checked against a calibrated test gauge. The test gauge reads 100 psi and the riser gauge reads 108 psi. What is the result under NFPA 25?
Answer: Passes: 8 psi is within 3% of full scale. Gauges are replaced or tested every 5 years against a calibrated gauge, and must be accurate to within 3 percent of full scale. For a 300 psi gauge that is 9 psi, so an 8 psi error passes. Measuring the error against the reading instead of the full scale is the usual mistake.
9. A high-rise has a sprinkler pressure-reducing valve on each floor. What test schedule does NFPA 25 set for these valves?
Answer: A partial flow test every year and a full flow test every 5 years. Each sprinkler pressure-reducing valve gets a partial flow test annually, enough to move the valve off its seat, and a full flow test at 5-year intervals with readings compared to previous results. The valves are also inspected quarterly. Swapping the two intervals is the classic error.
10. Staff run a diesel engine-driven fire pump weekly without flow and shut it down after 10 minutes, the same as the site's electric pump. Is this compliant with NFPA 25?
Answer: No: diesel engines must run at least 30 minutes on test. The weekly no-flow test runs electric motor-driven pumps for at least 10 minutes but diesel engine-driven pumps for at least 30 minutes, so the engine reaches operating temperature and problems show up. The weekly test is at churn, not at rated flow; flow tests are annual.
11. A site has 850 sprinklers in total. Under NFPA 25, what is the minimum number of spare sprinklers that must be kept on the premises?
Answer: 12. The minimum stock is 6 spares for up to 300 sprinklers, 12 for 300 to 1,000, and 24 for more than 1,000. The spares must cover each type and temperature rating installed, and a special sprinkler wrench for each type must be kept with them.
12. A dry barrel hydrant in a freezing climate has its drain plugged, as required by the local water utility. It has just been flow tested. What maintenance does NFPA 25 require?
Answer: Pump the water out of the barrel after the hydrant operates. Dry barrel hydrants in areas subject to freezing that have plugged drains must be pumped out after each operation, because the water cannot drain away and would freeze. Removing the plug is not the owner's call where it was plugged for a reason such as a high water table, and antifreeze is not used in hydrants.
13. Before winter, what maintenance does NFPA 25 require on the low points of a dry pipe sprinkler system?
Answer: Drain the low point drains (drum drips) to remove condensate. Dry pipe systems collect condensate at low points, which can freeze and split the pipe. NFPA 25 requires the low point drains to be drained before the onset of freezing weather and as needed through the season. Extra air pressure does not remove water, and antifreeze is not placed in dry systems.
14. During the 5-year internal piping assessment, the end-of-branch-line sprinkler removed from a wet system contains rust nodules and sediment. What does NFPA 25 require next?
Answer: Conduct an obstruction investigation of the affected system. The 5-year assessment opens a flushing connection at the end of one main and removes a sprinkler near the end of one branch line. Finding foreign organic or inorganic material triggers an obstruction investigation under Chapter 14, followed by flushing or other corrective work as needed. Simply resetting the 5-year clock leaves a blocked system.
15. A sprinkler system is being shut down for a planned riser repair. Under NFPA 25, where must the impairment tag be posted?
Answer: At each fire department connection and system control valve. A tag system shows that a system or part of it is out of service. NFPA 25 requires the tag at each fire department connection and system control valve, so responding firefighters and staff know which system is impaired. The alarm panel alone would not warn crews at the FDC.

Get the full CSITMS prep

Most popular · cancel anytime

Premium Monthly

$147/month
per exam
About $4.83 a day · less than a single code book, for a certification employers and AHJs ask for by name
  • One NFPA exam of your choice: CFPS, CFI or CFPE
  • 3,000 practice questions + 6 full mock exams per exam
  • 800 flashcards + 60 key notes per exam, by topic, plus mind maps
  • Spaced repetition + mistakes bank
  • Readiness Score & detailed reports
  • Video lessons as they release
  • Content updates during your access
  • 5 bonuses: formulas and values sheet, code values quick reference, study planner and more
  • Pass Guarantee: complete the prep, pass or 100% back

Renews monthly until you cancel. Cancel in two clicks from your account; you keep access until the end of the month you've paid for. No minimum term.

Best value · 3 months free

Premium Yearly

$1,323/year
per exam
Pay for 9 months, get 12. Save $441 against paying monthly.
  • One NFPA exam of your choice: CFPS, CFI or CFPE
  • 3,000 practice questions + 6 full mock exams per exam
  • 800 flashcards + 60 key notes per exam, by topic, plus mind maps
  • Spaced repetition + mistakes bank
  • Readiness Score & detailed reports
  • Video lessons as they release
  • Content updates during your access
  • 5 bonuses: formulas and values sheet, code values quick reference, study planner and more
  • Pass Guarantee: complete the prep, pass or 100% back

Renews once a year until you cancel. We email you before each renewal. Cancel any time from your account; you keep access until the end of the year you've paid for.

Pass Guarantee. Complete the full prep, sit your exam within 60 days, and if you don't pass we refund 100% of your subscription payments. See the requirements
Secure checkout by Stripe Card, Apple Pay, Google Pay Pass Guarantee

CSITMS exam FAQ

How many questions are on the CSITMS exam?

100 multiple-choice questions, with a time limit of 3 hours maximum. Format: open book: the official printed nfpa 25, standard for the inspection, testing, and maintenance of water-based fire protection systems (the edition named by the exam body), is the only reference allowed in the exam room. you must bring your own copy.

What is the passing score for CSITMS?

Not published by NFPA; results are reported as pass or fail only, with a diagnostic report by content area.

How much does the CSITMS exam cost?

US$499 initial application and exam; US$249 retest; US$225 recertification every 3 years. Fees and reference editions change, so confirm on nfpa.org before you apply.

Which languages is the CSITMS exam offered in?

English only.

Where do I take the CSITMS exam?

Prometric (proctored computer-based exam at in-person test centers worldwide).

Is this CSITMS practice test free?

Yes. The 15-question practice test on this page is free, with an explanation for every answer and no signup. A free account also unlocks the complete study notes for the first topic. The full CSITMS prep is Premium at $147 a month for this exam.

What's in the premium CSITMS prep?

3,000 practice questions organized topic by topic (General Requirements: 500; Inspection: 500; Testing: 500; Maintenance: 500; Internal Piping Condition and Obstruction Investigation: 500; Impairments: 500), 6 full-length timed mock exams of 100 questions, 800 flashcards and 60 comprehensive key notes split across all 6 topics, plus a mistakes bank and the Readiness Score.