ICC Fire Inspector II (67) Exam Study Guide (2026)
Everything the Fire Inspector II (67) tests, topic by topic: what each section covers, the facts that come up most, and how to study it. Pair it with the free 15-question practice test.
The exam at a glance
| Questions | 50 multiple-choice questions, four options each |
|---|---|
| Time | 2 hours |
| Passing score | Scaled score of 75 (ICC national certification standard); ICC does not publish the raw percentage, which varies by exam form |
| Format | Open book. ICC's catalog lists the International Building Code and International Fire Code (both also provided as free digital references during the exam) and IFSTA Fire Inspection and Code Enforcement. Bound, copyrighted books are allowed; study guides and practice questions are not. A second version of the exam uses a different edition of the IBC and IFC: pick the code edition when you buy the exam |
| Certifying body | International Code Council (ICC) |
| Test provider | ICC PRONTO: in person at a test center or online with remote proctoring |
Mind map: the whole exam on one screen
Read the complete ICC Fire Inspector II (67) study notes for “General Inspection Administration”
Our first full set of comprehensive notes, about 12 minutes of reading: Permits · Inquiries, research and communication · Reports, records and complaints · Enforcement, appeals and legal proceedings · Scheduling, a worked exam example, the traps examiners use and a one-minute recap. Create a free account to read it and see how premium notes work before you decide.
1. General Inspection Administration
20% of the exam, split into ten 2% tasks: communication, responding to inquiries, inspection reports, research, permitting, recordkeeping, complaints, appeals correspondence, legal proceedings and scheduling. Most answers are in IFC Chapter 1.
Key facts
- IFC Chapter 1 sets the fire code official's duties: right of entry, permits, notices, stop work orders, unsafe conditions and the board of appeals.
- Operational permits cover hazardous activities and events; construction permits cover installing or modifying systems and equipment.
- An inspection report records the date, location, conditions observed, code sections violated, required corrections and a reinspection date.
- Research order: the adopted code first, then standards it references, then commentary. Code provisions govern over a referenced standard where they conflict.
- Complaints are logged, investigated by inspection, and closed in writing with the findings and any action taken.
- Testimony is limited to facts you observed and records you made, so write reports as if a court will read them.
- The board of appeals hears claims about interpretation, applicability or equivalent protection, and it cannot waive the code.
Flashcards
Exam tip: Ten tasks at 2% each means no single task is worth much, but together they are one-fifth of the exam. Tab IFC Chapter 1 and read it once from start to finish.
2. Means of Egress, Emergency Access and Emergency Planning
Means of egress (6%), emergency access (2%) and emergency planning (4%): 12% of the exam. IFC Chapters 4, 5 and 10, with matching provisions in IBC Chapter 10.
Key facts
- Exit access travel distance (Table 1017.2): Groups A, E, F-1, M, R and S-1 are 200 ft unsprinklered and 250 ft sprinklered; Group B is 200 ft and 300 ft.
- Dead-end corridors: 20 ft base, 50 ft in listed sprinklered groups, and no limit where the length is under 2.5 times the least width.
- Two exits are needed above the Table 1006.2.1 occupant limit: 49 for most groups, 29 for Group S, 10 for Group R and most Group I, and 3 for H-1 to H-3.
- Fire apparatus access roads: 20 ft clear width, 13 ft 6 in. vertical clearance, and within 150 ft of all portions of the first story exterior walls.
- Dead-end access roads over 150 ft need an approved turnaround.
- Evacuation drill frequency is in IFC Table 405.2 by occupancy; plans are required for the occupancies listed in Section 403.
- Egress illumination: 1 foot-candle at the walking surface in normal operation, with 90 minutes of emergency power.
Flashcards
Exam tip: Egress tables reward quick lookups. Put a tab on Table 1006.2.1, Table 1017.2 and Section 1020 before exam day.
3. Construction Types, Exposures and Fire Flow Testing
Types of construction (2%), inspection for construction type (2%), exposures (2%) and fire flow testing (4%): 10% of the exam. IBC Chapter 6 and Table 601, IFC Chapter 5 and Appendix B, and the IFSTA manual.
Key facts
- Types I and II are noncombustible; Type III has noncombustible exterior walls; Type IV is heavy timber or mass timber; Type V allows any permitted material.
- A suffix A means protected (generally 1-hour or better); B means unprotected for most elements.
- Table 601 gives element ratings; Table 602 gives exterior wall ratings by fire separation distance.
- Fire separation distance is measured to the lot line, street centerline or an imaginary line between buildings on one lot.
- A flow test uses a test hydrant for static and residual pressure and a flow hydrant for pitot pressure.
- Available flow at 20 psi residual is the usual benchmark and is calculated with the 0.54 exponent.
- Pitot flow is calculated from the outlet diameter, discharge coefficient and velocity pressure.
Flashcards
Exam tip: Do flow test arithmetic twice. A wrong exponent gives an answer that often appears as a distractor.
Test yourself on these topics
Take the free 15-question ICC Fire Inspector II (67) test, then save your results to unlock your Readiness Score and the mistakes bank.
4. Fire Protection Systems: Readiness, Inspection and Plan Comparison
Equipment and system readiness (6%), fire protection inspection (4%) and comparing approved plans to installed systems (4%): 14% of the exam. IFC Chapter 9 and the systems sections of the IFSTA manual.
Key facts
- IFC Section 901.6 requires systems to be inspected, tested and maintained; records are kept on the premises.
- A required system out of service triggers immediate notice and, where required, evacuation or a fire watch.
Flashcards
Exam tip: When a stem says a system is out of service, look for the answer that includes notification, not just repair.
5. Occupancy Classification and Number of Occupants
Occupancy classification (4%) and number of occupants (8%): 12% of the exam. IBC Chapter 3 and Table 1004.5, repeated in IFC Chapter 10.
Key facts
- A-1 fixed seats for viewing performances; A-2 food and drink; A-3 worship, recreation and other assembly; A-4 indoor sports with spectator seating; A-5 outdoor.
- Group E is K through 12 education and day care for more than 5 children older than 2.5 years.
Flashcards
Exam tip: Occupant load is 8% of the exam, the largest task in this domain. Write down each area and factor on scratch paper before adding.
6. Occupancy Inspections
Performing fire safety inspections for various occupancy types: 10% of the exam, the largest single task. Applies the IFC general precautions, Chapter 10 and system rules to particular groups.
Key facts
- Assembly inspections focus on posted occupant load, exits, aisles, panic hardware and crowd managers.
- Panic hardware is required on doors serving Group A or E rooms with 50 or more occupants and in Group H.
Flashcards
Exam tip: Pick the occupancy first. Most mistakes come from applying a rule that belongs to a different group.
7. Industrial and Commercial Processes
Verifying code compliance of industrial and commercial processes and operations: 8% of the exam. IFC Part IV, including motor fuel dispensing, spray finishing, dry cleaning, hot work and lumber or woodworking operations.
Key facts
- Dispensing devices are 10 ft from lot lines and from combustible walls or openings, and 20 ft from fixed sources of ignition.
- Emergency disconnects for exterior dispensers are within 100 ft of, but not less than 20 ft from, the dispensers.
Flashcards
Exam tip: Part IV chapters are organized by process. Find the process in the table of contents first, then read the general requirements section.
8. Storage, Handling and Interior Finishes
Storage, handling and use of regulated materials (10%) and interior finish, furnishings and decorative materials (4%): 14% of the exam. IFC Part V and Chapter 8, with IBC Chapter 8.
Key facts
- Control areas are limited by floor: 4 at 100% on the first floor, 3 at 75% on the second, 2 at 50% on the third.
- The fourth to sixth floors allow 2 control areas at 12.5% each, separated by 2-hour barriers.
Flashcards
Exam tip: Do MAQ questions in order: base quantity, sprinkler increase, cabinet increase, then the floor percentage.
How to pass
- 50 questions in 120 minutes is 2.4 minutes each. Occupant load (8%) and flow test questions take longest, so answer the quick administration items first.
- Occupancies and regulated materials are 44% of this exam. Tab IBC Table 1004.5, the IBC Chapter 3 occupancy descriptions, IFC Table 5003.1.1(1) and Table 5003.8.3.2.
- Read every exception and table footnote. Sprinkler allowances often exclude a group, and hazardous material increases sit in the notes under the table.
- Administration is 20% across ten 2% tasks. Read IFC Chapter 1 closely, because permits, appeals and records are easy marks if you know where they are.
Frequently asked questions
How long should I study for the ICC Fire Inspector II (67) exam?
Most working candidates need 4 to 8 weeks at 45 to 60 minutes a day. Book your exam once your Readiness Score has stayed at 80 or higher for about a week.
Can I take the ICC Fire Inspector II (67) exam online?
NFPA delivers this exam at Prometric in-person computer-based test centers; it is not offered as a remote exam on NFPA's current pages. Format: open book. ICC's catalog lists the International Building Code and International Fire Code (both also provided as free digital references during the exam) and IFSTA Fire Inspection and Code Enforcement. Bound, copyrighted books are allowed; study guides and practice questions are not. A second version of the exam uses a different edition of the IBC and IFC: pick the code edition when you buy the exam. Check the NFPA Certification Candidate Handbook for the rules.
What score do I need to pass the ICC Fire Inspector II (67) exam?
Scaled score of 75 (ICC national certification standard); ICC does not publish the raw percentage, which varies by exam form. The exam has 50 multiple-choice questions, four options each and a time limit of 2 hours.
What are the most tested topics?
The outline covers general inspection administration, means of egress, emergency access and emergency planning, construction types, exposures and fire flow testing, fire protection systems: readiness, inspection and plan comparison, occupancy classification and number of occupants, occupancy inspections, industrial and commercial processes, storage, handling and interior finishes. Use the free practice test to see which ones you need most.
The premium ICC Fire Inspector II (67) study path
Premium ICC Fire Inspector II (67) prep is studied one topic at a time. Each step starts with that topic's key notes and flashcard deck, then its own question sets of 25, so you master one topic before you move to the next. When every topic is strong, the 6 full mock exams show you're ready.
Your step-by-step study path
- 1General Inspection Administration8 key notes, 100 flashcards, then 375 practice questions in 15 sets of 25Notes free with an account
- 2Means of Egress, Emergency Access and Emergency Planning8 key notes, 100 flashcards, then 375 practice questions in 15 sets of 25Premium
- 3Construction Types, Exposures and Fire Flow Testing8 key notes, 100 flashcards, then 375 practice questions in 15 sets of 25Premium
- 4Fire Protection Systems: Readiness, Inspection and Plan Comparison8 key notes, 100 flashcards, then 375 practice questions in 15 sets of 25Premium
- 5Occupancy Classification and Number of Occupants7 key notes, 100 flashcards, then 375 practice questions in 15 sets of 25Premium
- 6Occupancy Inspections7 key notes, 100 flashcards, then 375 practice questions in 15 sets of 25Premium
- 7Industrial and Commercial Processes7 key notes, 100 flashcards, then 375 practice questions in 15 sets of 25Premium
- 8Storage, Handling and Interior Finishes7 key notes, 100 flashcards, then 375 practice questions in 15 sets of 25Premium
- Final step: 6 full mock exams50 questions each, timed like test day. Pass them, then book your exam.Premium
Get every note, flashcard and question
Premium Monthly
- One NFPA exam of your choice: CFPS, CFI or CFPE
- 3,000 practice questions + 6 full mock exams per exam
- 800 flashcards + 60 key notes per exam, by topic, plus mind maps
- Spaced repetition + mistakes bank
- Readiness Score & detailed reports
- Video lessons as they release
- Content updates during your access
- 5 bonuses: formulas and values sheet, code values quick reference, study planner and more
- Pass Guarantee: complete the prep, pass or 100% back
Renews monthly until you cancel. Cancel in two clicks from your account; you keep access until the end of the month you've paid for. No minimum term.
Premium Yearly
- One NFPA exam of your choice: CFPS, CFI or CFPE
- 3,000 practice questions + 6 full mock exams per exam
- 800 flashcards + 60 key notes per exam, by topic, plus mind maps
- Spaced repetition + mistakes bank
- Readiness Score & detailed reports
- Video lessons as they release
- Content updates during your access
- 5 bonuses: formulas and values sheet, code values quick reference, study planner and more
- Pass Guarantee: complete the prep, pass or 100% back
Renews once a year until you cancel. We email you before each renewal. Cancel any time from your account; you keep access until the end of the year you've paid for.
Summarized from NFPA's official candidate information and the rules cited, checked November 2026. Confirm current requirements with International Code Council (ICC).